P846/EN CM/D
Commissioning
(CM) 10-12
MiCOM P846
5.1.4
External wiring
Check that the external wiring is correct to the relevant relay diagram and scheme
diagram. Ensure as far as practical that phasing/phase rotation appears to be as
expected. The relay diagram number appears on the rating label under the top access
cover on the front of the relay.
If a P991 test block is provided, the connections should be checked against the scheme
(wiring) diagram. It is recommended that the supply connections are to the live side of the
test block colored orange with the odd numbered terminals (1, 3, 5, 7 etc.). The auxiliary
supply is normally routed via terminals 13 (supply positive) and 15 (supply negative), with
terminals 14 and 16 connected to the relay’s positive and negative auxiliary supply terminals
respectively. However, check the wiring against the schematic diagram for the installation to
ensure compliance with the customer’s normal practice.
5.1.5
Watchdog contacts
Using a continuity tester, check that the watchdog contacts are in the states given in Table 2
for a de-energized relay.
Contact State
Terminals
Relay De-energized
Relay Energized
M11 – M12
(P846)
Closed
Open
M13 – M14
(P846)
Open
Closed
Table 2:
Watchdog contact status
5.1.6
Auxiliary supply
The relay can be operated from either a dc only or AC/DC auxiliary supply depending on the
relay’s nominal supply rating. The incoming voltage must be within the operating range
specified in Table 3.
Without energizing the relay, measure the auxiliary supply to ensure it is within the operating
range.
Nominal Supply Rating DC [AC rms]
DC Operating Range AC Operating Range
24 - 48V
[-]
19 to 65V
-
48 - 110V
[30 - 100V]
37 to 150V
24 - 110V
125 - 250V
[100 - 240V]
87 to 300V
80 to 265V
CM
Table 3:
Operational range of auxiliary supply Vx
It should be noted that the relay can withstand an ac ripple of up to 12% of the upper rated
voltage on the dc auxiliary supply.
Do not energize the relay or interface unit using the battery charger with the battery
disconnected as this can irreparably damage the relay’s power supply circuitry.
Energize the relay only if the auxiliary supply is within the specified operating ranges. If a
test block is provided, it may be necessary to link across the front of the test plug to connect
the auxiliary supply to the relay.
5.2
With the relay energized
The following group of tests verify that the relay hardware and software is functioning
correctly and should be carried out with the auxiliary supply applied to the relay.
The current and voltage transformer connections must remain isolated from the relay for
these checks. The trip circuit should also remain isolated to prevent accidental operation of
the associated circuit breaker.
Summary of Contents for MiCOM P846
Page 2: ......
Page 4: ......
Page 5: ...Safety Section P846 EN SS H11 SS SAFETY SECTION...
Page 6: ...P846 EN SS H11 Safety Section SS...
Page 8: ...P846 EN SS H11 Safety Section SS 2 SS...
Page 16: ...P846 EN IT D Introduction MiCOM P846 IT...
Page 18: ...P846 EN IT D Introduction IT 1 2 MiCOM P846 IT...
Page 26: ...P846 EN TD D Technical Data MiCOM P846 TD...
Page 38: ...P846 EN GS D Getting Started MiCOM P846 GS...
Page 58: ...P846 EN ST D Getting Started MiCOM P846 ST...
Page 60: ...P846 EN ST D Settings ST 4 2 MiCOM P846 ST...
Page 78: ...P846 EN OP D Operation MiCOM P846 OP...
Page 104: ...P846 EN OP D Operation OP 5 26 MiCOM P846 OP...
Page 106: ...P846 EN AP D Application Notes MiCOM P846 AP...
Page 108: ...P846 EN AP D Application Notes AP 6 2 MiCOM P846 AP...
Page 122: ...P846 EN AP D Application Notes AP 6 16 MiCOM P846 AP...
Page 124: ...P846 EN PL D Programmable Logic MiCOM P846 PL...
Page 126: ...P846 EN PL D Programmable Logic PL 7 2 MiCOM P846 PL...
Page 144: ...P846 EN MR D Measurements and Recording MiCOM P846 MR...
Page 146: ...P846 EN MR D Measurements and Recording MR 8 2 MiCOM P846 MR...
Page 160: ...P846 EN FD D Firmware Design MiCOM P846 FD...
Page 182: ...P846 EN CM D Commissioning MiCOM P846 CM...
Page 228: ...P846 EN CM D Commissioning CM 10 46 MiCOM P846 CM...
Page 230: ...P846 EN MT D Maintenance MiCOM P846 MT...
Page 232: ...P846 EN MT D Maintenance MT 11 2 MiCOM P846 MT...
Page 238: ...P846 EN TS D Troubleshooting MiCOM P846 TS...
Page 240: ...P846 EN TS D Troubleshooting TS 12 2 MiCOM P846 TS...
Page 252: ...P846 EN SC D SCADA Communications MiCOM P846 SC...
Page 272: ...P846 EN SG D Symbols and Glossary MiCOM P846 SG...
Page 280: ...P846 EN SG D Symbols and Glossary SG 14 8 MiCOM P846 SG...
Page 282: ...P846 EN IN D Installation MiCOM P846 IN...
Page 284: ...P846 EN IN D Installation IN 15 2 MiCOM P846 IN...
Page 296: ...P846 EN IN D Installation IN 15 14 MiCOM P846 IN...
Page 297: ......