P846/EN SC/D
SCADA Communications
(SC) 13-8
MiCOM P846
SC
REAR PORT2 (RP2)
The next cell down indicates the language, which is fixed at Courier for RP2.
RP2
protocol
Courier
The next cell down indicates the status of the hardware, e.g.
RP2
card
statu
EIA(RS)232
OK
s
The next cell allows for selection of the port configuration.
RP2 port config.
EIA(RS)232
The port can be configu
S)232, EIA(RS)485 or K-Bus.
In the case of EIA(RS)2
S)485 the next cell selects the communication mode.
red for EIA(R
32 and EIA(R
RP2
comms.
mode
IEC60870
FT1.2
The choice is either IEC60870 FT1.2 for normal operation with 11-bit modems, or 10-bit no
parity.
The next cell down con
rt address.
RP2
address
trols the comms. po
255
Since up to 32 relays c
necessary for each rela
an be connected to one K-bus spur, as indicated in Figure 2, it is
y to have a unique address so that messages from the master control
e master station to
communicate with the relay. The default value is 255 and must be changed in the range 0 to
The next cell down controls the inactivity timer.
er
15
mins.
station are accepted by one relay only. Courier uses an integer number between 0 and 254
for the relay address that is set with this cell. It is important that no two relays have the
same Courier address. The Courier address is then used by th
254 before use.
RP2 inactivity tim
The inactivity timer controls how long the relay will wait without receiving any messages on
the rear port before it reverts to its default state, including revoking any password access
that was enabled. For the rear port this can be set between 1 and 30 minutes.
In the case of EIA(RS)232 and EIA(RS)485 the next cell down controls the baud rate. For
K-Bus the baud rate is fixed at 64kbit/second between the relay and the KITZ interface at the
end of the relay spur.
Summary of Contents for MiCOM P846
Page 2: ......
Page 4: ......
Page 5: ...Safety Section P846 EN SS H11 SS SAFETY SECTION...
Page 6: ...P846 EN SS H11 Safety Section SS...
Page 8: ...P846 EN SS H11 Safety Section SS 2 SS...
Page 16: ...P846 EN IT D Introduction MiCOM P846 IT...
Page 18: ...P846 EN IT D Introduction IT 1 2 MiCOM P846 IT...
Page 26: ...P846 EN TD D Technical Data MiCOM P846 TD...
Page 38: ...P846 EN GS D Getting Started MiCOM P846 GS...
Page 58: ...P846 EN ST D Getting Started MiCOM P846 ST...
Page 60: ...P846 EN ST D Settings ST 4 2 MiCOM P846 ST...
Page 78: ...P846 EN OP D Operation MiCOM P846 OP...
Page 104: ...P846 EN OP D Operation OP 5 26 MiCOM P846 OP...
Page 106: ...P846 EN AP D Application Notes MiCOM P846 AP...
Page 108: ...P846 EN AP D Application Notes AP 6 2 MiCOM P846 AP...
Page 122: ...P846 EN AP D Application Notes AP 6 16 MiCOM P846 AP...
Page 124: ...P846 EN PL D Programmable Logic MiCOM P846 PL...
Page 126: ...P846 EN PL D Programmable Logic PL 7 2 MiCOM P846 PL...
Page 144: ...P846 EN MR D Measurements and Recording MiCOM P846 MR...
Page 146: ...P846 EN MR D Measurements and Recording MR 8 2 MiCOM P846 MR...
Page 160: ...P846 EN FD D Firmware Design MiCOM P846 FD...
Page 182: ...P846 EN CM D Commissioning MiCOM P846 CM...
Page 228: ...P846 EN CM D Commissioning CM 10 46 MiCOM P846 CM...
Page 230: ...P846 EN MT D Maintenance MiCOM P846 MT...
Page 232: ...P846 EN MT D Maintenance MT 11 2 MiCOM P846 MT...
Page 238: ...P846 EN TS D Troubleshooting MiCOM P846 TS...
Page 240: ...P846 EN TS D Troubleshooting TS 12 2 MiCOM P846 TS...
Page 252: ...P846 EN SC D SCADA Communications MiCOM P846 SC...
Page 272: ...P846 EN SG D Symbols and Glossary MiCOM P846 SG...
Page 280: ...P846 EN SG D Symbols and Glossary SG 14 8 MiCOM P846 SG...
Page 282: ...P846 EN IN D Installation MiCOM P846 IN...
Page 284: ...P846 EN IN D Installation IN 15 2 MiCOM P846 IN...
Page 296: ...P846 EN IN D Installation IN 15 14 MiCOM P846 IN...
Page 297: ......