Select Output 1 Range
Select Output 2 Range
Select Output 3 Range
Select Output 4 Range
Output Range
-10 to +10 vdc
0
0
0 to +10 vdc
0
1
4 to 20 mA
1
0
Not connected
1
1
Code:
Your value
Required initial value
loaded by ProSet 600
0 or 1
Blank Worksheets
Appendix A
A-2
Worksheet 3C
Select Output Ranges for your Valves
Control Word MCC04Bxx
15
14 13 12 11
10
09 08 07 06 05 04 03 02 01 00
ProSet 600 B34/bit
575 574 573 572 571 570 569 568 567 566 565 564 563 562 561 560
Value
1
1
1
1
1
1
1
1
Example: If you select 0-10 vdc for all four output ranges,
MCC04 = 11111111 01010101.
Important: Software input/output selections must match the jumper
settings for each respective input/output.