(4) Installation of air return duct
The unit is with air return and is set as back return type when out of factory. When installation, it can be
changed to down return type.
Ceiling Concealed type indoor unit must be with air return duct when installation, as figure 3 and 4:
Ceiling
Air supply
Air return
A
Building roof
Air return box
0.5m or 5m
Air supply duct
Unit
Fig. 3
no obstacles
within 1m
Air outlet
grille
Fig. 4(for A)
Air supply
Unit
Air return
Air return box
Every air sending duct and air return duct shall be fixed on the ceiling prefabricated panel by the iron
bracket. The duct joint is sealed with the glue. The recommended distance between the edge of the air
return duct and the wall is over 150mm.
The distance from the air outlet of the duct to the air outlet of the air conditioner is decided by the
length of duct and static pressure terminal:
Installation of short and long ducts is as below figure, when connecting the short ducts, use the low
static pressure terminals, which is white, the distance from the air outlet of the duct to the air outlet of
the air conditioner shall be no more than 0.5 m; When connecting the long ducts, use the middle static
pressure terminals, which is red. The distance from the air outlet of the duct to the air outlet of the air
conditioner shall be no more than 5m.
Fan speed selection (when using high efficient filter)
The fan motor composes red terminal and white terminal, which has been set at standard position when
out of factory. When the static pressure is increased for using high efficient filter, you can change the
connector position on the side of electric control box.
Standard Style(set in Factory)
Yellow
Black
Blue
Red
Yellow
Orange
Black
Blue
Control Box
Fan motor terminal
Control Box
Yellow
Black
Red
Blue
Yellow
Black
Red
Blue
High Speed Style
Static pressure range Unit: Pa
Standard static pressure
Max. static pressure
0
20
Fan motor terminal
73
Summary of Contents for YCV280
Page 1: ...Design Installation and Maintenance instruction R410A Heat Pump 50 Hz FlowLogic II 2016...
Page 5: ...2 External appearance YCV280 Outdoor YCV335 YCV400 YCV450 5...
Page 13: ...This range it 13...
Page 18: ...18...
Page 34: ...4 Piping diagram liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 34...
Page 62: ...4 Piping diagrams liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 62...
Page 83: ...4 Piping diagrams liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 83...
Page 135: ...AQXQVO LQIOZIU fckoc jcj_ a m jcj_ FFV cfn_l cfn_l h ch iil b_ n _r b ha_l 135...
Page 170: ...C 938 1046 186 5 234 2 6 5 2 9 9 A B MODEL 3 Dimensions HAV007 16 HAV018 24 170...
Page 171: ...4 Piping diagrams liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 171...
Page 178: ...Installation 8 178...
Page 179: ...179...
Page 180: ...HAV018 24 HAV007 16 180...
Page 181: ...181...
Page 185: ...9QTMUZQVUZ 86 97 6 96 8 786 8MU MY VN OYI Q 185...
Page 186: ...0 CQWQUO LQIOYITZ hemqe lela c o lela GGX behpan behpan b j ej kkn da p at_d jcan 186...
Page 200: ...N PR 6 MkjZeeh Sd_ji 62A B yt F vwv 200...
Page 206: ...206...
Page 208: ...208...
Page 209: ...209...
Page 210: ...210...
Page 211: ...211...
Page 212: ...212...
Page 249: ...E Capacity compensation value at different piping length and drop 255...
Page 280: ...286...
Page 298: ...RWV02 FlowLogic 304...
Page 309: ...Installation and connections Dimensions Connecting board 315...
Page 315: ...Ports Each port have serial number like 1 2 3 8 System Brief 321...
Page 322: ...Next Next Next 328...
Page 325: ...Select system DNS Click and add 331...
Page 327: ...3 Software installation Next 333...
Page 331: ...337...