3. Outdoor control
(1) Compressor startup control
On startup, inverter compressor will keep for 3 min at 60rps, then if TdiSH is still less than 25degree,
compressor will increase frequency up to 100rps. If startup is for 15min or TdiSH is more than 25degree,
quit startup and enter normal operation. In startup operation, the limitation frequency operation will
be in priority, such as high pressure too high, discharging temp. too high, suction pressure too low,
overcurrent.
After entering normal operation, when inverter compressor frequency arrives 100rps, fixed frequency
compressor starts up, but if inverter compressor frequency is down to below 30rps, fixed frequency
compressor is OFF.
(2) Compressor operation control
It will be controlled by the target pressure.
In heating mode, the target high pressure:
When Ta>-7degree, target high pressure is 28Kg 0.8Kg;
When Ta<=-7degree, target high pressure is 24Kg 0.8Kg
In cooling mode, the target low pressure
When the running indoor capacity is over 5HP, if Ta>=21degree, target pressure Ps=8Kg (4degree)
0.5Kg; if 21degree>Ta>=15degree, target pressure Ps=7Kg(0degree) 0.5Kg.
(3) Fan motor control
a. In cooling mode
Startup procedure: When compressor starts up, outdoor motor will not run right now, when high pressure
reaches 2.1MPa, outdoor motor begins to run.
In operation, the motor will be controlled by high pressure. When high pressure reaches 2.1MPa,
outdoor motor will run at class-1 speed; if pressure is more than 2.1MPa, outdoor motor will increase
one class at interval of 60 seconds; if pressure is over 2.6MPa, outdoor motor will rise up to class-7.
If pressure is less than 1.9MPa for 60 seconds, fan motor will decrease one class. If less than 1.8MPa
for 60 seconds, fan motor will stop.
b. In heating mode
Motor control in startup procedure: Pd<set p0.3MPa.If Pd goes up, decrease outdoor motor
speed. 1 minute later, if Pd>=(set pr0.50MPa), outdoor motor stops. When defrosting is over,
after 4-way valve opens, fan motor starts up.
In operation, the motor will be controlled by low pressure. When low pressure is over 0.95MPa, fan
motor will stop; when low pressure is less than 0.75MPa, for every 60 seconds, fan speed will increase
one class; when it is less than 0.65MPa for 60 seconds, fan speed will be class-7 directly.
In defrosting, outdoor motor will stop. After the defrosting is over, 4-way vavle opens, outdoor motor
will start up at heating mode.
(4) Defrosting control
When one of the running outdoors reaches the defrosting condition, it will send defrosting signal to
the master unit. After the master unit receives defrosting signal, it will send defrosting signal to the
running outdoor. Then the slave outdoor will begin defrosting.
369
Summary of Contents for YCV280
Page 1: ...Design Installation and Maintenance instruction R410A Heat Pump 50 Hz FlowLogic II 2016...
Page 5: ...2 External appearance YCV280 Outdoor YCV335 YCV400 YCV450 5...
Page 13: ...This range it 13...
Page 18: ...18...
Page 34: ...4 Piping diagram liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 34...
Page 62: ...4 Piping diagrams liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 62...
Page 83: ...4 Piping diagrams liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 83...
Page 135: ...AQXQVO LQIOZIU fckoc jcj_ a m jcj_ FFV cfn_l cfn_l h ch iil b_ n _r b ha_l 135...
Page 170: ...C 938 1046 186 5 234 2 6 5 2 9 9 A B MODEL 3 Dimensions HAV007 16 HAV018 24 170...
Page 171: ...4 Piping diagrams liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 171...
Page 178: ...Installation 8 178...
Page 179: ...179...
Page 180: ...HAV018 24 HAV007 16 180...
Page 181: ...181...
Page 185: ...9QTMUZQVUZ 86 97 6 96 8 786 8MU MY VN OYI Q 185...
Page 186: ...0 CQWQUO LQIOYITZ hemqe lela c o lela GGX behpan behpan b j ej kkn da p at_d jcan 186...
Page 200: ...N PR 6 MkjZeeh Sd_ji 62A B yt F vwv 200...
Page 206: ...206...
Page 208: ...208...
Page 209: ...209...
Page 210: ...210...
Page 211: ...211...
Page 212: ...212...
Page 249: ...E Capacity compensation value at different piping length and drop 255...
Page 280: ...286...
Page 298: ...RWV02 FlowLogic 304...
Page 309: ...Installation and connections Dimensions Connecting board 315...
Page 315: ...Ports Each port have serial number like 1 2 3 8 System Brief 321...
Page 322: ...Next Next Next 328...
Page 325: ...Select system DNS Click and add 331...
Page 327: ...3 Software installation Next 333...
Page 331: ...337...