yes
[39-0, 39-1] low pressure too low and compression ratio too high
no
no
no
yes
yes
no
open stop valve
re-connect the terminals
yes
check if system is lack
of refrigerant
check if terminal of
electronic expansion valve
coil is fixed well
check if piping system is
clogged
if actual pressure is in
conformance with the measured
data by sensor
recharge refrigerant
check if stop valve is open
fully
replace pressure sensor
yes
clear the piping
yes
[39-2] compression ratio too low
no
no
yes
yes
check compressor
check if 4-way valve is
interconnected
if actual pressure is in
conformance with the measured
data by sensor
replace 4-way valve
check if compressor
running current is normal
replace pressure sensor
392
Summary of Contents for YCV280
Page 1: ...Design Installation and Maintenance instruction R410A Heat Pump 50 Hz FlowLogic II 2016...
Page 5: ...2 External appearance YCV280 Outdoor YCV335 YCV400 YCV450 5...
Page 13: ...This range it 13...
Page 18: ...18...
Page 34: ...4 Piping diagram liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 34...
Page 62: ...4 Piping diagrams liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 62...
Page 83: ...4 Piping diagrams liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 83...
Page 135: ...AQXQVO LQIOZIU fckoc jcj_ a m jcj_ FFV cfn_l cfn_l h ch iil b_ n _r b ha_l 135...
Page 170: ...C 938 1046 186 5 234 2 6 5 2 9 9 A B MODEL 3 Dimensions HAV007 16 HAV018 24 170...
Page 171: ...4 Piping diagrams liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 171...
Page 178: ...Installation 8 178...
Page 179: ...179...
Page 180: ...HAV018 24 HAV007 16 180...
Page 181: ...181...
Page 185: ...9QTMUZQVUZ 86 97 6 96 8 786 8MU MY VN OYI Q 185...
Page 186: ...0 CQWQUO LQIOYITZ hemqe lela c o lela GGX behpan behpan b j ej kkn da p at_d jcan 186...
Page 200: ...N PR 6 MkjZeeh Sd_ji 62A B yt F vwv 200...
Page 206: ...206...
Page 208: ...208...
Page 209: ...209...
Page 210: ...210...
Page 211: ...211...
Page 212: ...212...
Page 249: ...E Capacity compensation value at different piping length and drop 255...
Page 280: ...286...
Page 298: ...RWV02 FlowLogic 304...
Page 309: ...Installation and connections Dimensions Connecting board 315...
Page 315: ...Ports Each port have serial number like 1 2 3 8 System Brief 321...
Page 322: ...Next Next Next 328...
Page 325: ...Select system DNS Click and add 331...
Page 327: ...3 Software installation Next 333...
Page 331: ...337...