(5) Oil return operation control
1. Entering condition
When outdoor total running capacity is over 25% and less than 75% for 4 hours, or outdoor total running
capacity is less than 25% for 2 hours, the system will enter oil return operation.
* When outdoor total running capacity is over 75% for 10 minutes continuously, the oil return time will
be cleared.
* In defrosting operation, when outdoor total running capacity is over 75% for 5 minutes continuously,
the oil return time will be cleared.
2. Oil return procedure:
All outdoors start up, and run with 75% of total capacity in cooling mode;
In oil return course, outdoor leva1, 2 open to 250pls;
In oil return course, THERMO ON, indoor valves 250pls, THERMO OFF, indoor valves 125pls; when Tdi
or Toil is over 105degree, indoor valve will open larger 10%.
In oil return, Levb OFF.
temp. sensor TA, any outdoor can meet the below conditions for 5 minutes, all the outdoors will enter
defrosting operation.
a. when TE<= -6degree for 5 minutes;
b. when -6<TA<5, -13.6<TE<-6 for 5 minutes, enter defrosting;
c. TA<-6, TE<= -15 for 5 minutes, and compressor has run for 90 minutes between the two defrostings;
In defrosting operation:
a. 4-way valve OFF
b. outdoor motor OFF
c. anti-cold air control of indoor motor OFF
d. outdoor EEV OFF
Quit defrosting
Any of the below conditions can be met, the unit will quit defrosting.
a. After defrosting begins, 10 minutes later, defrosting is over;
b. Detect the defrosting condition of outdoor heat exchanger by TE, all the temperatures at the defrosting
point are over 10 degree for 60 seconds or reaches 15 degree or 10 seconds, quit defrosting;
c. High pressure Pd is over 35kgG/cm2, quit defrosting.
Entering condition:
When the unit has run in heating mode for 33 minutes and the compressor has run for 50 minutes
accumulatively since the last defrosting. By measuring the defrosting sensor TE and outdoor ambient
370
Summary of Contents for YCV280
Page 1: ...Design Installation and Maintenance instruction R410A Heat Pump 50 Hz FlowLogic II 2016...
Page 5: ...2 External appearance YCV280 Outdoor YCV335 YCV400 YCV450 5...
Page 13: ...This range it 13...
Page 18: ...18...
Page 34: ...4 Piping diagram liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 34...
Page 62: ...4 Piping diagrams liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 62...
Page 83: ...4 Piping diagrams liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 83...
Page 135: ...AQXQVO LQIOZIU fckoc jcj_ a m jcj_ FFV cfn_l cfn_l h ch iil b_ n _r b ha_l 135...
Page 170: ...C 938 1046 186 5 234 2 6 5 2 9 9 A B MODEL 3 Dimensions HAV007 16 HAV018 24 170...
Page 171: ...4 Piping diagrams liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 171...
Page 178: ...Installation 8 178...
Page 179: ...179...
Page 180: ...HAV018 24 HAV007 16 180...
Page 181: ...181...
Page 185: ...9QTMUZQVUZ 86 97 6 96 8 786 8MU MY VN OYI Q 185...
Page 186: ...0 CQWQUO LQIOYITZ hemqe lela c o lela GGX behpan behpan b j ej kkn da p at_d jcan 186...
Page 200: ...N PR 6 MkjZeeh Sd_ji 62A B yt F vwv 200...
Page 206: ...206...
Page 208: ...208...
Page 209: ...209...
Page 210: ...210...
Page 211: ...211...
Page 212: ...212...
Page 249: ...E Capacity compensation value at different piping length and drop 255...
Page 280: ...286...
Page 298: ...RWV02 FlowLogic 304...
Page 309: ...Installation and connections Dimensions Connecting board 315...
Page 315: ...Ports Each port have serial number like 1 2 3 8 System Brief 321...
Page 322: ...Next Next Next 328...
Page 325: ...Select system DNS Click and add 331...
Page 327: ...3 Software installation Next 333...
Page 331: ...337...