H. Set EEV open angle by hand
When being switched off, short connect CN27 to open the valve fully compulsorily for 2 minutes;
When being switched off, short connect CN29 to close the valve fully compulsorily for 2 minutes.
I. Anti-freezed protection
In cooling mode, execute the anti-freezed protection due to the measured indoor coil temp. to avoid
the indoor heat exchanger causeing frost or ice.
J. Other functions
a. Swing motor control
Indoor will control swing motor ON/OFF due to the swing signal from wired controller.
b. Auxiliary electric heater control
In heating mode, if the below conditions can be met, the electric heater will work:
(1) Indoor fan motor and compressor are running;
(4) Unit stops or quit the heating mode.
c. Filter cleaning
Check and memorize the running time of indoor fan motor, once arriving the requested time (set
by SW07-6), indoor will send filter cleaning signal to wired controller; when indoor recieves the filter
reset signal from wired controller, if the time exceeds the requested time, the filter will reset.
d. Compulsory defrosting: after indoor receives the compulsory defrosting signal from wired controller,
it will send compulsory defrosting signal to outdoor contineously for 10 times. In the sending period,
indoor will execute the normal defrost.
e. Trial operation
Set the mode as cooling (heating), press ON/OFF for 5 seconds to enter compulsory cooling (heating).
In compulsory cooling, display "LL" and COOL will flash;
In compulsory heating, display "HH" and HEAT will flash, fan speed is AUTO.
At this time, only ON/OFF, TEMP +/- are valid.
,5- @dm dig`o o`hk1 dn ij hjm` oc\i 55~>
,6- Qjjh o`hk1 dn gjr`m jq`m 5~ oc\i oc` n`o o`hk1>
,7- Bjhkm`nnjm c\n mpi ajm 8 n`^ji_n>
Ddoc`m ]`gjr ^ji_dodji dn h`o/oc` `g`^omd^ c`\o`m rdgg nojk=
,4- Hi_jjm a\i hjojm jm ^jhkm`nnjm ijo mpin>
,5- Hi_jjm \dm dig`o o`hk1 dn jq`m 56~>
,6- Hi_jjm \dm dig`o o`hk1 dn cdbc`m jq`m 04~ oc\i oc` n`o o`hk1>
355
Summary of Contents for YCV280
Page 1: ...Design Installation and Maintenance instruction R410A Heat Pump 50 Hz FlowLogic II 2016...
Page 5: ...2 External appearance YCV280 Outdoor YCV335 YCV400 YCV450 5...
Page 13: ...This range it 13...
Page 18: ...18...
Page 34: ...4 Piping diagram liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 34...
Page 62: ...4 Piping diagrams liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 62...
Page 83: ...4 Piping diagrams liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 83...
Page 135: ...AQXQVO LQIOZIU fckoc jcj_ a m jcj_ FFV cfn_l cfn_l h ch iil b_ n _r b ha_l 135...
Page 170: ...C 938 1046 186 5 234 2 6 5 2 9 9 A B MODEL 3 Dimensions HAV007 16 HAV018 24 170...
Page 171: ...4 Piping diagrams liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 171...
Page 178: ...Installation 8 178...
Page 179: ...179...
Page 180: ...HAV018 24 HAV007 16 180...
Page 181: ...181...
Page 185: ...9QTMUZQVUZ 86 97 6 96 8 786 8MU MY VN OYI Q 185...
Page 186: ...0 CQWQUO LQIOYITZ hemqe lela c o lela GGX behpan behpan b j ej kkn da p at_d jcan 186...
Page 200: ...N PR 6 MkjZeeh Sd_ji 62A B yt F vwv 200...
Page 206: ...206...
Page 208: ...208...
Page 209: ...209...
Page 210: ...210...
Page 211: ...211...
Page 212: ...212...
Page 249: ...E Capacity compensation value at different piping length and drop 255...
Page 280: ...286...
Page 298: ...RWV02 FlowLogic 304...
Page 309: ...Installation and connections Dimensions Connecting board 315...
Page 315: ...Ports Each port have serial number like 1 2 3 8 System Brief 321...
Page 322: ...Next Next Next 328...
Page 325: ...Select system DNS Click and add 331...
Page 327: ...3 Software installation Next 333...
Page 331: ...337...