3. Inspection before trial operation
Before inspection, confirm the state of indoor and outdoor to avoid the trial failure because of the
incorrect installation.
3.1 Indoor unit confirmation
3.2 Outdoor unit confirmation
No.
inspection items
results
1
If indoor unit is in good condition, and if the electric box position is in
accordance with the state when out of factory, also if it is fixed firmly.
2
If indoor wiring is correct. If the connecting terminal of the fan motor,
swing motor and water pump is connected well. If the sensor is in good
condition and it is at the proper place.
3
If the dip switch of indoor unit is set correctly. If the indoor address, central
controller address, wired controller address and its other selection are
correct.
4
If the wire sequence of wired controller is correct.
5
Before being electrified, measure the resistors among live wire, neutral
wire and earthing point on the terminal block with the 500V ohmmeter. The
resistor must be over 1 M Ohm.
No.
inspection items
results
1
If outdoor unit is in good condition, and if the electric box is fixed firmly.
2
If outdoor wiring is correct. If the wires are broken.
3
If the dip switch of outdoor unit is set correctly. If the outdoor address is
correct. The master unit No. must be No.1, and the other units can be No.
2, No.3. If there are multiple outdoors, before being electrified, the master
unit SW4-5 is set as "searching outdoor".
4
if the communication wire between indoor and outdoor is connected to
master unit, or the master unit will occur failure code 1002.
5
Before being electrified, measure the resistors among live wire, neutral
wire and earthing point on the terminal block with the 500V ohmmeter. The
resistor must be over 1 M Ohm.
293
Summary of Contents for YCV280
Page 1: ...Design Installation and Maintenance instruction R410A Heat Pump 50 Hz FlowLogic II 2016...
Page 5: ...2 External appearance YCV280 Outdoor YCV335 YCV400 YCV450 5...
Page 13: ...This range it 13...
Page 18: ...18...
Page 34: ...4 Piping diagram liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 34...
Page 62: ...4 Piping diagrams liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 62...
Page 83: ...4 Piping diagrams liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 83...
Page 135: ...AQXQVO LQIOZIU fckoc jcj_ a m jcj_ FFV cfn_l cfn_l h ch iil b_ n _r b ha_l 135...
Page 170: ...C 938 1046 186 5 234 2 6 5 2 9 9 A B MODEL 3 Dimensions HAV007 16 HAV018 24 170...
Page 171: ...4 Piping diagrams liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 171...
Page 178: ...Installation 8 178...
Page 179: ...179...
Page 180: ...HAV018 24 HAV007 16 180...
Page 181: ...181...
Page 185: ...9QTMUZQVUZ 86 97 6 96 8 786 8MU MY VN OYI Q 185...
Page 186: ...0 CQWQUO LQIOYITZ hemqe lela c o lela GGX behpan behpan b j ej kkn da p at_d jcan 186...
Page 200: ...N PR 6 MkjZeeh Sd_ji 62A B yt F vwv 200...
Page 206: ...206...
Page 208: ...208...
Page 209: ...209...
Page 210: ...210...
Page 211: ...211...
Page 212: ...212...
Page 249: ...E Capacity compensation value at different piping length and drop 255...
Page 280: ...286...
Page 298: ...RWV02 FlowLogic 304...
Page 309: ...Installation and connections Dimensions Connecting board 315...
Page 315: ...Ports Each port have serial number like 1 2 3 8 System Brief 321...
Page 322: ...Next Next Next 328...
Page 325: ...Select system DNS Click and add 331...
Page 327: ...3 Software installation Next 333...
Page 331: ...337...