Note 1: Temp. difference between air inlet and air outlet Standard
A. In cooling mode, after running for at least 30 minutes, it is normal that the temp. difference between
air inlet and air outlet is over 10 , (at max. frequency)
B. In heating mode, after running for at least 30 minutes, it is normal that the temp. difference between
air inlet and air outlet is over 14 , (at max. frequency).
Note 2: Running current standard
It is normal that the running current is in the range of rated current
(at max. frequency) . The
current will be different for the below condition:
if more than the rated current: high indoor/outdoor temp. ; outdoor bad ventilation (cooling mode),
indoor bad ventilation (heating mode).
if lower than rated current: low indoor/outdoor temp.; refrigerant leakage (lack of refrigerant).
Note 3: Running pressure standard
indoor 18~32
outdoor 25~35
indoor 15~25
outdoor 5~10
cooling
(at max. frequency)
heating
(at max. frequency)
high pressure 2.0~3.5MPa
low pressure 0.6~1.0MPa
high pressure 2.2~2.8MPa
low pressure 0.3~0.8MPa
The above value is measured after running for 15 minutes (ambient temp. is DB )
High/low pressure changing trend due to the running condition:
Cooling/heating:
indoor temp. goes up---high/low pressure goes up
indoor temp. goes down---high/low pressure goes down
outdoor temp. goes up---high/low pressure goes up
outdoor temp. goes down---high/low pressure goes down
e
e
c[_h
e
e
e
e
e
303
Summary of Contents for YCV280
Page 1: ...Design Installation and Maintenance instruction R410A Heat Pump 50 Hz FlowLogic II 2016...
Page 5: ...2 External appearance YCV280 Outdoor YCV335 YCV400 YCV450 5...
Page 13: ...This range it 13...
Page 18: ...18...
Page 34: ...4 Piping diagram liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 34...
Page 62: ...4 Piping diagrams liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 62...
Page 83: ...4 Piping diagrams liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 83...
Page 135: ...AQXQVO LQIOZIU fckoc jcj_ a m jcj_ FFV cfn_l cfn_l h ch iil b_ n _r b ha_l 135...
Page 170: ...C 938 1046 186 5 234 2 6 5 2 9 9 A B MODEL 3 Dimensions HAV007 16 HAV018 24 170...
Page 171: ...4 Piping diagrams liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 171...
Page 178: ...Installation 8 178...
Page 179: ...179...
Page 180: ...HAV018 24 HAV007 16 180...
Page 181: ...181...
Page 185: ...9QTMUZQVUZ 86 97 6 96 8 786 8MU MY VN OYI Q 185...
Page 186: ...0 CQWQUO LQIOYITZ hemqe lela c o lela GGX behpan behpan b j ej kkn da p at_d jcan 186...
Page 200: ...N PR 6 MkjZeeh Sd_ji 62A B yt F vwv 200...
Page 206: ...206...
Page 208: ...208...
Page 209: ...209...
Page 210: ...210...
Page 211: ...211...
Page 212: ...212...
Page 249: ...E Capacity compensation value at different piping length and drop 255...
Page 280: ...286...
Page 298: ...RWV02 FlowLogic 304...
Page 309: ...Installation and connections Dimensions Connecting board 315...
Page 315: ...Ports Each port have serial number like 1 2 3 8 System Brief 321...
Page 322: ...Next Next Next 328...
Page 325: ...Select system DNS Click and add 331...
Page 327: ...3 Software installation Next 333...
Page 331: ...337...