Table 7: SRU configuration data (continued)
Data
type
Designation
Functionality
Value
range
Default
editable via
RFID reader?
editable via
SCROLL
command?
u8
u8InitialLampState_B
State Lamp 2 after powering the
SRU: 0 = OFF, 1 = ON
0, 1
0
yes
yes
u8
u8SequencedSwitchingEnabled Sequenced switching using
remote address
0, 1
1
yes
yes
u8
u8ExtendedFlags
0x01= RFID activated
Bit
0x01
yes
no
26 Bytes
4.7.7 Configuring a SRU for LED Lights
Refer to
Configuring a SRU — Advanced Parameters
section.
UM-5005, Rev. 004, 2020/08/06