4.8 CCRE Interrelations
4.8.1 Constant Current Regulator Type E — Interface
The CCRE
®
interface is structured in the following way:
Figure 45: CCR display
4.8.2 Constant Current Regulator type E — nominal Current
The Constant Current Regulator must at series circuit nominal current (6.6 A) be set to the correct current flow duration of the
thyristor.
•
The correct working point guarantees sufficient control reserves and low harmonic distortion.
•
By choosing the correct output voltage tap of the transformer, the following conducting time should be achieved:
~ 6.1 ms without RELIANCE remotes,
~ 5.8 ms when using the ADB SAFEGATE RELIANCE IL
RELIANCE Intelligent Lighting
Operation
60
Copyright
©
ADB SAFEGATE, All Rights Reserved