5.7.2 Self-test Feature without RFID reader DRH100 — SRU Type 111 and 112
In SRU111 and SRU112 is a self-test feature implemented. See
Functional Description Self-test Feature
for test result message
description.
The types 111 and 112 limit voltage using a switch that measures SRU output and limits it. The self-test can be triggered with
the RFID reader DRH100 using a CCRE and the lucDMC maintenance tool. Individual remotes can be tested this way. The self-
test can also triggered in the series circuit for all remotes installed in the circuit.
DANGER
The self-test feature serves only as an additional tool, but does not guarantee absolute safety. It keeps being a device
testing itself, but it can be used as a technical aid. The self-test feature serves only as an additional maintenance tool.
It is not meant to replace the check with an external measurement device.
DANGER
Make sure you switch off the regulator before you connect the regulator to the series circuit.
Follow the following steps to execute a self-test for a single remote using an RFID reader DRH100:
1. Start the lucDMC tool.
2. Select an airport for the project from the drop-down list in the start window.
Figure 72: Log-in window — location selection airport
Figure 73: List of selected airports example
3. Type a station name in the station field. See dialog box above.
4. Check the box group change in ...programming when the remotes are configured.
5. Select the CCR with SCROLL tab.
6. Go to CCR settings and navigate to advanced settings > default .
7.
8. Set the self-test to ON instead of OFF.
9. Select the highest brightness level 7 that equals by default 6,6 A.
UM-5005, Rev. 004, 2020/08/06
95
Copyright
©
ADB SAFEGATE, All Rights Reserved
Summary of Contents for RELIANCE Intelligent Lighting Platform III
Page 1: ...RELIANCE Intelligent Lighting Platform III User Manual UM 5005 Rev 004 2020 08 06 ...
Page 2: ......
Page 10: ...RELIANCE Intelligent Lighting List of Figures x Copyright ADB SAFEGATE All Rights Reserved ...
Page 12: ...RELIANCE Intelligent Lighting List of Tables xii Copyright ADB SAFEGATE All Rights Reserved ...
Page 18: ...RELIANCE Intelligent Lighting Safety 6 Copyright ADB SAFEGATE All Rights Reserved ...
Page 52: ...RELIANCE Intelligent Lighting Introduction 40 Copyright ADB SAFEGATE All Rights Reserved ...
Page 56: ...RELIANCE Intelligent Lighting Installation 44 Copyright ADB SAFEGATE All Rights Reserved ...
Page 118: ......