120
3.
Read Data (Function Code 03)
Query
This function allows the master to obtain the measurement results from the meter.
Table 5-8 depicts reading slave device (address 17) Inline A real-time energy, Inline B real-
time energy, , Inline C real-time energy (these parameters are dword data type, each
parameter uses 2 addresses, each address uses 2 bytes). AcuRev 2000 Inline A real-time
energy address is 2500H, 2501H; Inline B real-time energy address is 2502H, 2503H; Inline C
real-time energy is 2504H, 2505H.
Addr
Fun
Data start
addr hi
Data start
Addr lo
Data #of
regs hi
Data #of
regs lo
CRC16
hi
CRC16
lo
11H
03H
25H
00H
00H
06H
CCH
54H
Table 5-8 Query of Inline A real-time energy, Inline B real-time energy, Inline C real-time energy
Response
Response frame contains slave device address, function code, data quantity and CRC check.
Table 5-9 depicts Inline A real-time energy=0000000BH(1.1kWh), Inline B real-time energy=
0000000CH(1.2kWh), Inline C real-time energy=0000000D(1.3kWh).
Addr
Fun
Byte
count
Data1
hi
Data1
Lo
Data 2
hi
Data2
lo
Data3
hi
Data3
lo
Data4
hi
Data4
lo
11H
03H
0CH
00H
00H
00H
0BH
00H
00H
00H
0CH
Data5
hi
Data5
Lo
Data 6
hi
Data6
lo
CRC16
hi
CRC16
lo
00H
00H
00H
0DH
21H
88H
Table 5-9 Response of Inline A real-time energy, Inline B real-time energy, Inline C real-time energy
Summary of Contents for AcuRev 2000
Page 1: ...User s Manual AcuRev 2000 Smart Metering System...
Page 2: ......
Page 8: ...VI...
Page 9: ...1 1 1 Meter Overview 1 2 Areas of Application 1 3 AcuRev 2000 features Chapter 1 Introduction...
Page 15: ...7 Chapter 2 Installation 2 1 Appearance and Dimensions 2 2 Installation Methods 2 3 Wiring...
Page 40: ...32...
Page 93: ...85 Figure 4 7 Demand...
Page 101: ...93 4 6 Over Under Limit Alarming Figure 4 13 Alarming in software...
Page 104: ...96 Figure 4 15 System Event Log 4 7 System Event Log...
Page 120: ...112 4 10 Device Information Figure 4 18 Device Information...
Page 152: ...144 Figure 5 18...
Page 158: ...150 Figure 5 23...