2. Set the max record number and Offset to the meter. Initially the Offset is 0. In this
example, set 0x0A0B and 0x0000 to 0x3B01 and 0x3B02.
3. Read the Window Status from 0x3B01, if the status says 0xFF, then go to step 2 to set max
record number and Offset again. If the status says 0x0B, the content of the window will be
read.
4. Read the window content and calculate the next record offset. The next record offset is
the last record offset plus the max record number per window. After completing, set the
new offset to 0x3B02.Then repeat step 3 until all the records are retrieved.
Basic Measurement
AcuRev 2010 only takes power related measurements. The format is floating point. Each
parameter uses 4 bytes, high bytes are followed by low bytes. Function Code: 03.Read only.
Address
Parameter
Property
Alarm parameter
label
Default
Data
Type
2000H-2001H
F
R
0
float
2002H-2003H
U1
R
1
float
2004-2005H
U2
R
2
float
2006-2007H
U3
R
3
float
2008-2009H
Uavg
R
4
float
200AH-200BH
U12
R
5
float
200CH-200DH
U23
R
6
float
200EH-200FH
U31
R
7
float
2010H-2011H
Ulavg
R
8
float
2012H-2013H
IL1(Phase A inline
current)
R
9
float
2014H-2015H
IL2(Phase B inline
current)
R
10
float
Summary of Contents for AcuRev 2000
Page 1: ...User s Manual AcuRev 2000 Smart Metering System...
Page 2: ......
Page 8: ...VI...
Page 9: ...1 1 1 Meter Overview 1 2 Areas of Application 1 3 AcuRev 2000 features Chapter 1 Introduction...
Page 15: ...7 Chapter 2 Installation 2 1 Appearance and Dimensions 2 2 Installation Methods 2 3 Wiring...
Page 40: ...32...
Page 93: ...85 Figure 4 7 Demand...
Page 101: ...93 4 6 Over Under Limit Alarming Figure 4 13 Alarming in software...
Page 104: ...96 Figure 4 15 System Event Log 4 7 System Event Log...
Page 120: ...112 4 10 Device Information Figure 4 18 Device Information...
Page 152: ...144 Figure 5 18...
Page 158: ...150 Figure 5 23...