122
5. Preset/Reset Multi-Register (Function Code 16)
Query
Function Code 16(10H Hex) allows the user to modify the contents of multiple
registers. The example below is a request to preset device address of 17's channel
#1's real-time energy as 12345.6 kWh. AcuRev 2000 energy is raw data multiplied by
0.1 kWh, therefore, the value written into the register should be 123456, hex format is
01E240H. Channel #1's real-time energy address is 2508H and 2509H, 32 bit, total 4 Bytes.
Addr
Fun
Data start
reg hi
Data start
reg lo
Data #of
reg hi
Data #of
reg lo
Byte
Count
11H
10H
25H
08H
00H
02H
04H
Value hi Value Lo
Value hi
Value lo
CRC hi
CRC lo
00H
01H
E2H
40H
18H
C8H
Table 5-12 Preset tenant #1's real-time energy
Response
The correct response is to send back address, function code, data starting address, data
bytes, CRC check after the value is changed.
Addr
Fun
Data start
reg hi
Data start
reg lo
Data #of
reg hi
Data #of
Reg lo
CRC16
hi
CRC16
lo
11H
10H
25H
08H
00H
02H
C9H
96H
Table 5-13 Preset Multi-reigster response frame
Summary of Contents for AcuRev 2000
Page 1: ...User s Manual AcuRev 2000 Smart Metering System...
Page 2: ......
Page 8: ...VI...
Page 9: ...1 1 1 Meter Overview 1 2 Areas of Application 1 3 AcuRev 2000 features Chapter 1 Introduction...
Page 15: ...7 Chapter 2 Installation 2 1 Appearance and Dimensions 2 2 Installation Methods 2 3 Wiring...
Page 40: ...32...
Page 93: ...85 Figure 4 7 Demand...
Page 101: ...93 4 6 Over Under Limit Alarming Figure 4 13 Alarming in software...
Page 104: ...96 Figure 4 15 System Event Log 4 7 System Event Log...
Page 120: ...112 4 10 Device Information Figure 4 18 Device Information...
Page 152: ...144 Figure 5 18...
Page 158: ...150 Figure 5 23...