94
Alarming records alarming timestamp, alarming parameter, over/under limit
value, alarming status and alarming condition. Users can setup alarming conditions in
"Alarm Setup". The maximum alarming record is 20.
Note: The alarming threshold value is not a real measured value, it is the percetage of real
measured value over rated value. For instance, if the rated value is 1100, the displayed
threshold is 40, then real value = rated value x percentage = 1100×40% = 440.
Please refer to Figure 4-11 for detailed setup.
Figure 4-14 Alarming Setup