Description of application and parameters
Application "Function block x"
Product manual 2CKA001473B9488
│70
11.5.4.3
Object type
Options:
1 bit
1 byte 0 - 100%
■
1 bit:
– The value is sent as 1-bit switching commands (up/down or adjustment).
■
1 byte 0 - 100%:
– The value is sent as 1-byte value without a sign (position in percent).
The parameter is used to set the size of communication objects for the control of blinds. For
selection "1 bit", objects "Sx: moving" and "Sx: adjusting" are available. For selection "1 byte 0-
100%", objects "Sx: position" and "Lx: slat position" are available.
If option "1 byte 0-100%" is selected, communication objects can be connected with 1-byte
position objects of the blind actuators. Also desired positions of the blind can be preset under
Extended parameters
.
Example: Button 1 always moves the blind down to 50%, with the slats closed at 50%. Button 1
always moves the blind down to 80%, with the slats closed at 100%.
Note
The parameter can only be set if the "Blind/roller blind function switchover"
parameter is set on "Blind".
11.5.4.4
Function switchover blinds/roller blinds
Options:
Blind
Roller blind
■
Blind:
– The application is fixed on blind control.
■
Roller blind:
– The application is fixed on roller blind control.
The parameter is used to specify whether the sensor or the selected button can be used for a
blind or a roller blind control.
Note
If the "Blind" function is selected and parameter "Object type" is fixed on "1 byte