Description of application and parameters
Application "General functions"
Product manual 2CKA001473B9488
│181
11.7.9.8
Scene can be saved
Options:
Deactivated
Activated
■
Deactivated:
– Stored scene values that are sent at a scene call-up via different actuator objects, can
not be changed and overwritten by the user.
■
Activated:
– Current scene values of actuator objects can be overwritten and stored in the device by
the user.
The parameter is used to specify whether the user can trigger a scene storage. The
communication objects "GFx: actuator groups x" in this case send read requests to the
connected actuators. Provided that the L-flag is set for the communication objects of the
connected actuators, these will send their current values to the device via an answer telegram.
The values are stored in the memory and overwrite the previous values. These are also not lost
in the event of a power failure.
11.7.9.9
Actuator group x
Options:
Deactivated
Activated
■
Deactivated:
– The value of actuator group x is not sent at the call-up of the scene.
■
Activated:
– The value of actuator group x is sent at the call-up of the scene.
The parameter is used to specify whether a telegram of actuator group x is sent at the call-up of
the light scene.
The possible options and setting limits depend on parameter "Object type actuator group x".
11.7.9.10
Number of light scene
Options:
Setting option from 1 to 64
Setting option, if parameter "Object type actuator group x" is set on "Light scene number".