Communication profiles
37
4
OFF_2_STA
1
OFF2 inactive
0
OFF2 ACTIVE
5
OFF_3_STA
1
OFF3 inactive
0
OFF3 ACTIVE
6
SWC_ON_
INHIB
1
SWITCH-ON INHIBITED
0
–
7
ALARM
1
Warning/Alarm
0
No warning/alarm
8
AT_
SETPOINT
1
OPERATING
. Actual value equals reference = is
within tolerance limits, i.e. in speed control, speed
error is 10% max. of the nominal motor speed.
0
Actual value differs from reference = is outside
tolerance limits.
9
REMOTE
1
Drive control location: REMOTE (EXT1 or EXT2)
0
Drive control location: LOCAL
10
ABOVE_
LIMIT
1
Actual frequency or speed equals or exceeds
supervision limit (set by drive parameter). Valid in
both directions of rotation.
0
Actual frequency or speed within supervision limit
11
EXT_CTRL_
LOC
1
External Control Location EXT2 selected
0
External Control Location EXT1 selected
12
EXT_RUN_E
NABLE
1
External Run Enable signal received
0
No External Run Enable signal received
13 to
14
Reserved
15
1
Communication error detected by fieldbus adapter
module
0
Fieldbus adapter communication OK
Status Word of the ABB Drives profile
Bit
Name
Value
STATE/Description