CANopen object dictionary
53
0×1010
0
Store
parameters
U8
RO
Largest supported subindex.
If the value of bit 0 of the
subindexes is 1, the device saves
parameters on command.
Parameters can be saved by writing
0x65766173 ("evas") to the relevant
subindex.
1
Save all
parameters
U32
RW
Stores all parameters to memory.
2
Save
communication
(objects
0×1000 …
0×1A16)
parameters
U32
RW
Communication parameters are not
stored in the module.
3
Save drive
profile (objects
0×603F…
0×60FE,
0×2001…
0×200B)
parameters
U32
RW
All profile parameters are saved.
4
Save drive
parameters
U32
RW
Store drive parameters.
Index
(hex)
Sub-
index
Name
Type
Attri-
bute
Information
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]