Emergency messages, DS301 and DS402
67
Emergency messages, DS301 and DS402
What this chapter contains
This chapter contains a list of the CANopen error codes.
Error codes
Error codes can be read from the objects 0×200B and 0×603F
(hex). Additionally, the MN can query the status of the CN with the
StatusResponse service. See chapter
Network Management
Services
.
Error codes between xx80…xxFF (hex) and between
FF00…FFFF (hex) are manufacturer specific. Descriptions for
these error codes can be found in the appropriate drive firmware
manual and/or the drive fault code parameter.
Error codes
Error
code (hex)
Meaning
0000
Error reset or no error
1000
Generic error
2000
Current
2100
Current on device input side
2110
Short circuit / earth leakage
2120
Earth leakage
2121
Earth leakage phase L1
2122
Earth leakage phase L2
2123
Earth leakage phase L3
2130
Short circuit
2131
Short circuit phases L1-L2
2132
Short circuit phases L2-L3
2133
Short circuit phases L3-L1
2200
Internal current
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]