ZAngPE
ZPE
1
p1
p2
ZPE
2
p3
ZPE
3
Ohm/phase
R
jX
en07000010.vsd
IEC07000010 V2 EN
Figure 57:
Proposed test points for phase-to-earth faults
Label
Description
ZPE1
The measured impedance for phase-to-earth fault at point 1 (zone reach ZPE) ohm/
phase.
ZAngPE
The characteristic angel for phase-to-earth fault in degrees.
ZPE2 and ZPE3 The fault impedance for phase-to-earth fault at the boundary for the zone reach at
point 2 and 3.
Table 25:
Test points for phase-to-phase loops L1-L2 (Ohm/Loop)
Test points
Set
Comments
1
ZPE · cos(ZAngPE)
ZPE · sin(ZAngPE)
2
ZPE/2 + ΔR = (ZPE/2) · (1 - cos(ZAngPE))
ZPE/2 · sin(ZAngPE)
3
ZPE/2 - ΔR = ZPE/2 · (1 - cos(ZAngPE))
ZPE/2 · sin(ZAngPE)
Check also in the same way as for phase-to-earth fault for each test point that the
output signals STPE, START and STLx are activated where x refers to the actual
phase to be tested. After the timer
tPE
for the zone has elapsed, also the signals
TRIP, TRPE and TRx shall be activated.
13.5.4
Faulty phase identification with load encroachment
FMPSPDIS
There is no specific test routine for this function. The function is tested in
conjunction with other impedance (mho) functions.
1MRK 504 088-UEN C
Section 13
Verifying settings by secondary injection
127
Installation and commissioning manual
Summary of Contents for RELION RET670
Page 1: ...Relion 670 series Transformer protection RET670 Installation and commissioning manual...
Page 2: ......
Page 16: ...10...
Page 24: ...18...
Page 26: ...20...
Page 28: ...22...
Page 82: ...76...
Page 88: ...82...
Page 94: ...88...
Page 104: ...98...
Page 110: ...104...
Page 210: ...204...
Page 230: ...224...
Page 239: ...233...