Universal Stopper Install

STI-13000 & STI-14000 Series

Specifications

Polycarbonate Enclosure
·  Flammability - flush and surface mount models (Fig. 2 & 3): UL 94 V-2, enclosed flush and  

 

  enclosed back box models (Fig. 4 & 5): UL 94 5VA
·  Cover wall thickness  0.125 inches
Gaskets   
STI-1318 3” Gasket - Neoprene 1/8” diameter
Mounting gasket (embedded in housing at STI factory prior to shipping) - Two part polyurethane
STI-6004 1/2” or 3/4” conduit weather gasket - Closed Cell Neoprene

Horn 9V 

(Battery included)

 12V 

24V

·  Low (95 dB @ 1 ft.) 

40mA 

38mA 

22mA

·  High (105 dB @ 1 ft.) 

105mA 

125mA 

95mA

·  Min.  Operating  Req. 

2V  @  20mA 

4V  @  20mA 

4V  @  20mA           

Dry Contact Relay
·  30 VAC/VDC, 1A

Temperature Range
·  Electronics operating range: -40° to 120°F (-40° to 49°C) 

Below -4°F (-20°C), a remote   

 

power source is recommended
·  Polycarbonate rated: -40° to 284°F (-40° to 140°C)

Installation Notes

·  When used outdoors, the manual station must also be rated for outdoor use.
·  UL Listing does not permit external power source or connection of horn relay contacts to fire alarm 

or life safety devices.

·  When properly installed, the operation of this cover will not interfere with the function of your life 

safety system.

·  Horn operation and performance must be tested annually.  Battery replacement is recommended 

annually dependent on usage and battery expiration date.

·  Ensure the service pin is properly inserted in the service pin receptor to silence horn while performing 

installation or servicing horn.

·  If mounting to an uneven surface, a backplate (STI-1314) is recommended to help ensure proper 

sealing to mounting surface. 

·  The backplate may be drilled if wire access or screw mounting holes are needed. 

4.08 in.

(104mm)

5.42 in.

(138mm)

4.96 in.

(126mm)

4.31 in.

(110mm)

3.25 in.

(83mm)

2.54 in.

(84mm)

2.66 in.

(68mm)

2.0 in.

(51mm)

1.5 in.

(38mm)

1.0 in.

(25mm)

FLUSH END VIEW

.67 in.

(17mm)

5.95 in.

(151mm)WITHOUT HORN

5.28 in.

(134mm)WITH HORN

.42 in.

(11mm)

5.42 in.

(138mm)WITH HORN

6.36 in.

(162mm)WITHOUT HORN

FLUSH SIDE VIEW

LIFT HERE

TEXT HERE

6.45 in.

(164mm)

2.73 in.

(69mm)

2.29 in.

(58mm)

4.58 in.

(116mm)

LIFT HERE

6.45 in.

(164mm)

2.73 in.

(69mm)

2.29 in.

(58mm)

4.58 in.

(116mm)

LIFT HERE

TEXT HERE

6.45 in.

(164mm)

2.73 in.

(69mm)

2.29 in.

(58mm)

4.58 in.

(116mm)

LOCKING
TAB

LOCKING
TAB

LOCKING
TAB

TEXT HERE

Fig. 1 - Dimensions

Center pull station to the Universal Stopper with the help of 
dimensions shown in 

Fig. 1.

Open cover, use frame or optional backplate to mark 
mounting holes.

NOTE: Be sure the entire cover travel will not interfere 
with operation of the pull station or other safety system 
equipment when installed.

Summary of Contents for 13000 Series

Page 1: ...ion of horn relay contacts to fire alarm or life safety devices When properly installed the operation of this cover will not interfere with the function of your life safety system Horn operation and performance must be tested annually Battery replacement is recommended annually dependent on usage and battery expiration date Ensure the service pin is properly inserted in the service pin receptor to...

Page 2: ...FACE DRILL 3 16 DIA HOLES 1 1 4 in DEEP WHEN USING ANCHORS DRILL 7 64 DIA HOLES 1 1 4 in DEEP WHEN ANCHORS ARE NOT USED LOCKING TAB DRILL 1 8 in HOLE WHILE COVER IS CLOSED INSERT THE BREAKAWAY SEAL SUB 65 COMPLETELY INTO THE LOCKING TAB NOT USED ON FIRE OR EMERGENCY SIGNAL APPLICATIONS WALL ANCHOR 4 PROVIDED 3 in GASKET APPLY A DROP OF SILICONE TO HOLD IN PLACE NOTE MAY BE TRIMMED FOR A PROPER FIT...

Page 3: ...AL BACK BOX MOUNTING HOLES 4 PROVIDED IP67 A 5 CONDUCTOR WIRE HARNESS SERVICE PIN 1 PROVIDED ROTATE BOTTOM END OF BATTERY UPWARD FOR REMOVAL HI LOW FACTORY DEFAULT HIGH VOLUME SWITCH 4 HI LO SCREW 2 PROVIDED WHEN REPLACING COVER MAKE SURE COVER IS UNDER HORN CASE TAB AND ROTATE COVER CLOSED INSERT HI LO SCREWS AND TIGHTEN HORN COVER REMOVE BOTH HORN SCREWS AND ROTATE COVER OPEN AS SHOWN HORN CASE ...

Page 4: ...n cas d utilisation sur les réseaux d incendie Le Universal Stopper est destiné à être utilisé dans les zones où l occurrence de fausses alertes d incendie issues d avertisseurs d incendie manuels est élevée ou présente un problème grave Un quelconque inconvénient de ce dispositif est vite contrecarré par les conséquences des fausses alertes d incendie surtout lorsque le personnel et l équipement ...

Reviews: