10.2
Optical budget calculation for serial communication
with LON
Table 18:
Example
Distance 1 km
Glass
Distance10 m
Plastic
Maximum attenuation
-11 dB
- 7 dB
4 dB/km multi mode: 820 nm - 62.5/125 um
4 dB
-
0.3 dB/m plastic: 620 nm - 1mm
-
3 dB
Margins for installation, aging, and so on
5 dB
2 dB
Losses in connection box, two contacts (0.75 dB/contact)
1.5 dB
-
Losses in connection box, two contacts (1dB/contact)
-
2 dB
Margin for repair splices (0.5 dB/splice)
0.5 dB
-
Maximum total attenuation
11 dB
7 dB
1MRK 504 088-UEN C
Section 10
Establishing connection and verifying the LON communication
97
Installation and commissioning manual
Summary of Contents for RELION RET670
Page 1: ...Relion 670 series Transformer protection RET670 Installation and commissioning manual...
Page 2: ......
Page 16: ...10...
Page 24: ...18...
Page 26: ...20...
Page 28: ...22...
Page 82: ...76...
Page 88: ...82...
Page 94: ...88...
Page 104: ...98...
Page 110: ...104...
Page 210: ...204...
Page 230: ...224...
Page 239: ...233...