ExV is supplied by the Node at end of the Bus Segment
The specifications of the components are:
a) Ru
+ 5 V to Signal B
= 390
W
, 0.25 W ±2.5%
b) Rt
Signal B to Signal A
= 220
W
, 0.25 W ±2.5%
c) Rd
Signal A to GND
= 390
W
, 0.25 W ±2.5%
2.3.3
Bus power distribution
The end node in each Ph-segment applies 5 V bus excitation power to the Termination network via
the Excitation pair (ExV+ and GND) used in the Type 3 Physical layer specification.
5.6.3
Data on RS485 serial communication module cable
Type:
Twisted-pair S-STP (Screened – Screened Twisted Pair)
Shield:
Individual foil for each pair with overall copper braid
Length:
Maximum 1200 m (3000 ft) from one system earth to the next system earth
(includes length from platform point to system earth on both sides)
Temp:
According to application
Impedance:
120
W
Capacitance:
Less than or equal to 42 pF/m
Example:
Belden 9841,Alpha wire 6412, 6413
5.7
Installing the GPS antenna
5.7.1
Antenna installation
The antenna is mounted on a console for mounting on a horizontal or vertical flat
surface or on an antenna mast.
Section 5
1MRK 504 088-UEN C
Installing the IED
70
Installation and commissioning manual
Summary of Contents for RELION RET670
Page 1: ...Relion 670 series Transformer protection RET670 Installation and commissioning manual...
Page 2: ......
Page 16: ...10...
Page 24: ...18...
Page 26: ...20...
Page 28: ...22...
Page 82: ...76...
Page 88: ...82...
Page 94: ...88...
Page 104: ...98...
Page 110: ...104...
Page 210: ...204...
Page 230: ...224...
Page 239: ...233...