IEC61850 Ed1 IEDs because in IEC61850 Ed1 only one access
point can be modelled in SCL.
The IP address can be set in
IP address
. ECT validates the value, the access points
have to be on separate subnetworks.
The subnetwork mask can be set in
Subnet mask
. This field will be updated to the
SCL model based on the
Subnetwork
selection.
To select which communication protocols can be run on the respective access
points, check or uncheck the check box for the relevant protocol. The protocols are
not activated/deactivated in ECT, only filtered for the specific access point. For
information on how to activate the individual communication protocols, see the
communication protocol chapters.
To increase security it is recommended to uncheck protocols that
are not used on the access point.
The default gateway can be selected by entering the IP address in
Default gateway
.
The default gateway is the router that is used to communicate with the devices in
the other subnetwork. By default this is set to
0.0.0.0
which means that no default
gateway is selected. ECT validates the entered value, but the default gateway has to
be in the same subnetwork as the access point. The default gateway is the router
that is being used as default, that is when no route has been set up for the
destination. If communication with a device in another subnetwork is needed, a
route has to be set up. For more information on routes, see the
Routes
chapter in the
Technical manual
and the
Application manual
.
DHCP can be activated for the front port from the LHMI in
Main menu/
Configuration/Communication/Ethernet configuration/Front port/DHCP:1
18.2
Redundant communication
18.2.1
Identification
GUID-B7AE0374-0336-42B8-90AF-3AE1C79A4116 v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
IEC 62439-3 Parallel redundancy
protocol
PRP
-
-
IEC 62439-3 High-availability seamless
redundancy
HSR
-
-
Access point diagnostic for redundant
Ethernet ports
RCHLCCH
-
-
Section 18
1MRK 511 407-UEN C
Ethernet-based communication
286
Phasor measurement unit RES670 2.2 IEC
Application manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 IEC Application manual...
Page 2: ......
Page 46: ...40...
Page 52: ...46...
Page 92: ...86...
Page 112: ...106...
Page 178: ...172...
Page 216: ...210...
Page 232: ...226...
Page 286: ...280...
Page 328: ...322...
Page 340: ...334...
Page 380: ...374...
Page 381: ...375...