IEC16000038-1-en.vsdx
AP1
PhyPortB
PhyPortA
AP1
PhyPortA
PhyPortB
AP1
PhyPortA
PhyPortB
AP1
PhyPortB
PhyPortA
Device 1
Device 2
Device 3
Device 4
IEC16000038 V1 EN-US
Figure 95:
High-availability Seamless Redundancy (HSR)
18.2.3
Setting guidelines
GUID-887B0AE2-0F2E-414D-96FD-7EC935C5D2D8 v1
Redundant communication is configured with the Ethernet configuration tool in
PCM600.
Redundancy
: redundant communication is activated when the parameter is set to
PRP-0
,
PRP-1
or
HSR
. The settings for the next access point will be hidden and
PhyPortB will show the second port information. Redundant communication is
activated after a common write to IED is done.
PRP-1
should be used primarily,
PRP-0
is intended only for use in existing PRP-
networks. PRP-1 and HSR can be combined in a mixed network.
If the access point is not taken into operation, the write option in Ethernet
Configuration Tool can be used to activate the access point.