XHiLim
: High limit. Set as % of
YBase
(Y is
SBase
for S,P,Q
UBase
for Voltage
measurement and
IBase
for current measurement).
XLowLim
: Low limit. Set as % of
YBase
(Y is
SBase
for S,P,Q
UBase
for Voltage
measurement and
IBase
for current measurement).
XLowLowLim
: Low-low limit. Set as % of
YBase
(Y is
SBase
for S,P,Q
UBase
for
Voltage measurement and
IBase
for current measurement).
XLimHyst
: Hysteresis value in % of range and is common for all limits.
All phase angles are presented in relation to defined reference channel. The
parameter
PhaseAngleRef
defines the reference.
Calibration curves
It is possible to calibrate the functions (CVMMXN, CMMXU, VMMXU and
VNMMXU) to get class 0.5 presentations of currents, voltages and powers. This is
accomplished by amplitude and angle compensation at 5, 30 and 100% of rated
current and voltage. The compensation curve will have the characteristic for
amplitude and angle compensation of currents as shown in figure
(example).
The first phase will be used as reference channel and compared with the curve for
calculation of factors. The factors will then be used for all related channels.
IEC05000652 V2 EN-US
Figure 86:
Calibration curves
Section 16
1MRK 511 407-UEN C
Monitoring
254
Phasor measurement unit RES670 2.2 IEC
Application manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 IEC Application manual...
Page 2: ......
Page 46: ...40...
Page 52: ...46...
Page 92: ...86...
Page 112: ...106...
Page 178: ...172...
Page 216: ...210...
Page 232: ...226...
Page 286: ...280...
Page 328: ...322...
Page 340: ...334...
Page 380: ...374...
Page 381: ...375...