via a PPS out from the GTM. If PTP is used in the IED and the merging unit
cannot be synchronized from the IED, then use GPS-based clocks to provide PTP
synch as well as sync to the merging unit.
If synchronization of the IED and the merging unit is based on GPS, set the
parameter
LostSyncMode
to
BlockOnLostUTC
in order to provide a block of
protection functions whenever the global common time is lost.
If PTP is not used, use the same synchronization method for the
HwSyncSrc
as the
merging unit provides. For instance, if the merging unit provides PPS as
synchronization, use PPS as
HwSyncSrc
. If either PMU or LDCM in GPS-mode is
used, that is, the hardware and software clocks are connected to each other,
HwSyncSrc
is not used and other means to synchronize the merging unit to the IED
is required. Either
FineSyncSource
is set to the same source that the merging unit
uses, or the PPS output from the GTM module is used to synchronize the merging
unit. If the PPS output from the GTM module is used to synchronize the merging
unit and PTP is not used, the IED does not know how the merging unit is
synchronized and the parameter
LostSyncMode
must be set to
NoBlock
.
Section 22
1MRK 511 407-UEN C
Basic IED functions
354
Phasor measurement unit RES670 2.2 IEC
Application manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 IEC Application manual...
Page 2: ......
Page 46: ...40...
Page 52: ...46...
Page 92: ...86...
Page 112: ...106...
Page 178: ...172...
Page 216: ...210...
Page 232: ...226...
Page 286: ...280...
Page 328: ...322...
Page 340: ...334...
Page 380: ...374...
Page 381: ...375...