23.1.7.1
Current transformers according to IEC 61869-2, class P, PR
M11623-6 v4
A CT according to IEC 61869-2 is specified by the secondary limiting e.m.f. E
ALF
.
The value of the E
ALF
is approximately equal to the corresponding E
al
. Therefore,
the CTs according to class P and PR must have a secondary limiting e.m.f. E
ALF
that fulfills the following:
ALF
alreq
E
max E
EQUATION1383 V4 EN-US
(Equation 102)
23.1.7.2
Current transformers according to IEC 61869-2, class PX, PXR (and
old IEC 60044-6, class TPS and old British Standard, class X)
M11623-14 v5
CTs according to these classes are specified approximately in the same way by a
rated knee point e.m.f. E
knee
(E
k
for class PX and PXR, E
kneeBS
for class X and the
limiting secondary voltage U
al
for TPS). The value of the E
knee
is lower than the
corresponding E
al
according to IEC 61869-2. It is not possible to give a general
relation between the E
knee
and the E
al
but normally the E
knee
is approximately 80 %
of the E
al
. Therefore, the CTs according to class PX, PXR, X and TPS must have a
rated knee point e.m.f. E
knee
that fulfills the following:
(
)
knee
k
kneeBS
al
alreq
E
E
E
U
0.8 maximum of E
»
»
»
>
×
EQUATION2100 V2 EN-US
(Equation 103)
23.1.7.3
Current transformers according to ANSI/IEEE
M11623-22 v6
Current transformers according to ANSI/IEEE are partly specified in different
ways. A rated secondary terminal voltage U
ANSI
is specified for a CT of class C.
U
ANSI
is the secondary terminal voltage the CT will deliver to a standard burden at
20 times rated secondary current without exceeding 10 % ratio correction. There
are a number of standardized U
ANSI
values for example, U
ANSI
is 400 V for a C400
CT. A corresponding rated equivalent limiting secondary e.m.f. E
alANSI
can be
estimated as follows:
alANSI
sr
ct
ANSI
sr
ct
sr
bANSI
E
20 I
R
U
20 I
R
20 I
Z
=
×
×
+
=
×
×
+
×
×
EQUATION971 V2 EN-US
(Equation 104)
where:
Z
bANSI
The impedance (that is, with a complex quantity) of the standard ANSI burden for the specific
C class (
W
)
U
ANSI
The secondary terminal voltage for the specific C class (V)
Section 23
1MRK 511 407-UEN C
Requirements
360
Phasor measurement unit RES670 2.2 IEC
Application manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 IEC Application manual...
Page 2: ......
Page 46: ...40...
Page 52: ...46...
Page 92: ...86...
Page 112: ...106...
Page 178: ...172...
Page 216: ...210...
Page 232: ...226...
Page 286: ...280...
Page 328: ...322...
Page 340: ...334...
Page 380: ...374...
Page 381: ...375...