7% 0, 07
x
pu
=
=
EQUATION1373 V1 EN-US
(Equation 85)
Equation
can be re-written in the following way without changing the value for
the operate time of the negative sequence inverse overcurrent IED:
2
2
1
op
NS
r
k
x
t
I
x I
×
=
æ
ö
ç
÷
×
è
ø
EQUATION1374 V1 EN-US
(Equation 86)
In order to achieve such protection functionality with one CVGAPC functions the
following must be done:
1. Connect three-phase generator currents to one CVGAPC instance (for
example, GF01)
2. Set parameter
CurrentInput
to value
NegSeq
3. Set base current value to the rated generator current in primary amperes
4. Enable one overcurrent step (for example, OC1)
5. Select parameter
CurveType_OC1
to value
Programmable
op
P
A
t
k
B
M
C
æ
ö
= ×
+
ç
÷
-
è
ø
EQUATION1375 V1 EN-US
(Equation 87)
where:
t
op
is the operating time in seconds of the Inverse Time Overcurrent TOC/IDMT algorithm
k
is time multiplier (parameter setting)
M
is ratio between measured current magnitude and set pickup current level
A, B, C and P are user settable coefficients which determine the curve used for Inverse Time
Overcurrent TOC/IDMT calculation
When the equation
characteristic of the OC1 it is obvious that if the following rules are followed:
1. set k equal to the generator negative sequence capability value
2. set
A_OC1
equal to the value 1/x2
3. set
B_OC1
= 0.0,
C_OC1
=0.0 and
P_OC1
=2.0
4. set
StartCurr_OC1
equal to the value x
then the OC1 step of the CVGAPC function can be used for generator negative
sequence inverse overcurrent protection.
Section 11
1MRK 511 407-UEN C
Multipurpose protection
198
Phasor measurement unit RES670 2.2 IEC
Application manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 IEC Application manual...
Page 2: ......
Page 46: ...40...
Page 52: ...46...
Page 92: ...86...
Page 112: ...106...
Page 178: ...172...
Page 216: ...210...
Page 232: ...226...
Page 286: ...280...
Page 328: ...322...
Page 340: ...334...
Page 380: ...374...
Page 381: ...375...