IEC07000198 V3 EN-US
Figure 120:
Configuration for using an instance in task time group 1 as DFT
reference
Assume instance SMAI7:7 in task time group 1 has been selected in the
configuration to control the frequency tracking . Observe that the selected reference
instance (i.e. frequency tracking master) must be a voltage type. Observe that
positive sequence voltage is used for the frequency tracking feature.
For task time group 1 this gives the following settings (see Figure
for
numbering):
SMAI1:1:
DFTRefExtOut
=
DFTRefGrp7
to route SMAI7:7 reference to the
SPFCOUT output,
DFTReference
=
DFTRefGrp7
for SMAI1:1 to use SMAI7:7 as
) SMAI2:2 – SMAI12:12:
DFTReference
=
DFTRefGrp7
for SMAI2:2 – SMAI12:12 to use SMAI7:7 as reference.
For task time group 2 this gives the following settings:
SMAI1:13 – SMAI12:24:
DFTReference
=
ExternalDFTRef
to use DFTSPFC
input of SMAI1:13 as reference (SMAI7:7)
For task time group 3 this gives the following settings:
SMAI1:25 – SMAI12:36:
DFTReference
=
ExternalDFTRef
to use DFTSPFC
input as reference (SMAI7:7)
Example 2
Section 22
1MRK 511 407-UEN C
Basic IED functions
346
Phasor measurement unit RES670 2.2 IEC
Application manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 IEC Application manual...
Page 2: ......
Page 46: ...40...
Page 52: ...46...
Page 92: ...86...
Page 112: ...106...
Page 178: ...172...
Page 216: ...210...
Page 232: ...226...
Page 286: ...280...
Page 328: ...322...
Page 340: ...334...
Page 380: ...374...
Page 381: ...375...