22.12.2
Setting guidelines
M15260-3 v7
Remember always that there are two possible ways to place the IED in the
TestMode
=
On
” state. If, the IED is set to normal operation (
TestMode
=
Off
), but
the functions are still shown being in the test mode, the input signal IED_TEST on
the TESTMODE function block is activated in the configuration.
Forcing of binary input and output signals is only possible when the IED is in IED
test mode.
22.13
Time synchronization TIMESYNCHGEN
IP1750-1 v2
22.13.1
Setting guidelines
IP15089-1 v3
All the parameters related to time are divided into two categories: System time and
Synchronization.
22.13.1.1
System time
M11348-119 v6
The system time can be set manually via the local HMI under
Main menu/
Configuration/Time/System time
. The time is set with years, month, day, hour,
minute, second and millisecond. In addition, there are also settings for Day-Light-
Saving and adjustment of Time-Zones.
22.13.1.2
Synchronization
M11348-143 v5
The setting parameters for the real-time clock with external time synchronization
are set via local HMI or PCM600. The path for Time Synchronization parameters
on local HMI is
Main menu/Configuration/Time/Synchronization
. The
parameters are categorized as Time Synchronization (TIMESYNCHGEN) and
IRIG-B settings (IRIG-B:1) in case that IRIG-B is used as the external time
synchronization source.
Time Synchronization
GUID-1F0B3D89-8323-430B-AF22-4076BBA882F0 v2
The time synchronization (TIMESYNCHGEN) parameters are divided in two
categories, "general" and "IEC61850-9-2" parameters.
The general parameters are as follows:
•
FineSynchSource
•
SynchMaster
FineSynchSource
: This parameter is used to select the time synchronization source.
The options are "Off", "GPS", "IRIG-B", or "GPS+IRIG-B". In case that both GPS
and IRIG-B are used (GPS+IRIG-B) for redundant time synchronization, the PMU
will automatically select the most accurate time synchronization source.
Section 22
1MRK 511 407-UEN C
Basic IED functions
350
Phasor measurement unit RES670 2.2 IEC
Application manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 IEC Application manual...
Page 2: ......
Page 46: ...40...
Page 52: ...46...
Page 92: ...86...
Page 112: ...106...
Page 178: ...172...
Page 216: ...210...
Page 232: ...226...
Page 286: ...280...
Page 328: ...322...
Page 340: ...334...
Page 380: ...374...
Page 381: ...375...