Operation
: With the parameter
Operation
the function can be set
On
/
Off
.
Mode
: The voltage and current used for the power measurement. The setting
possibilities are shown in table
.
Table 19:
Complex power calculation
Set value
Mode
Formula used for complex power calculation
L1, L2, L3
*
*
*
1
1
2
2
3
3
L
L
L
L
L
L
S
U
I
U
I
U
I
=
×
+
×
+
×
EQUATION1697 V1 EN-US
(Equation 69)
Arone
*
*
1 2
1
2 3
3
L L
L
L L
L
S
U
I
U
I
=
×
-
×
EQUATION1698 V1 EN-US
(Equation 70)
PosSeq
*
3
PosSeq
PosSeq
S
U
I
= ×
×
EQUATION1699 V1 EN-US
(Equation 71)
L1L2
*
*
1 2
1
2
(
)
L L
L
L
S
U
I
I
=
×
-
EQUATION1700 V1 EN-US
(Equation 72)
L2L3
*
*
2 3
2
3
(
)
L L
L
L
S
U
I
I
=
×
-
EQUATION1701 V1 EN-US
(Equation 73)
L3L1
*
*
3 1
3
1
(
)
L L
L
L
S
U
I
I
=
×
-
EQUATION1702 V1 EN-US
(Equation 74)
L1
*
1
1
3
L
L
S
U
I
= ×
×
EQUATION1703 V1 EN-US
(Equation 75)
L2
*
2
2
3
L
L
S
U
I
= ×
×
EQUATION1704 V1 EN-US
(Equation 76)
L3
*
3
3
3
L
L
S
U
I
= ×
×
EQUATION1705 V1 EN-US
(Equation 77)
The function has two stages that can be set independently.
With the parameter
OpMode1(2)
the function can be set
On
/
Off
.
The function gives trip if the power component in the direction defined by the
setting
Angle1(2)
is larger than the set pick up power value
Power1(2)
Section 8
1MRK 511 407-UEN C
Current protection
168
Phasor measurement unit RES670 2.2 IEC
Application manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 IEC Application manual...
Page 2: ......
Page 46: ...40...
Page 52: ...46...
Page 92: ...86...
Page 112: ...106...
Page 178: ...172...
Page 216: ...210...
Page 232: ...226...
Page 286: ...280...
Page 328: ...322...
Page 340: ...334...
Page 380: ...374...
Page 381: ...375...