19.6
IEC 60870-5-103 communication protocol
IP14615-1 v2
19.6.1
Application
IP14864-1 v1
M17109-3 v7
TCP/IP
Control Center
IED
IED
IED
Gateway
Star coupler
Station HSI
IEC05000660-4-en.vsd
IEC05000660 V4 EN-US
Figure 112:
Example of IEC 60870-5-103 communication structure for a
substation automation system
IEC 60870-5-103 communication protocol is mainly used when a protection IED
communicates with a third party control or monitoring system. This system must
have software that can interpret the IEC 60870-5-103 communication messages.
When communicating locally in the station using a Personal Computer (PC) or a
Remote Terminal Unit (RTU) connected to the Communication and processing
module, the only hardware needed is optical fibers and an opto/electrical converter
for the PC/RTU, or a RS-485 connection depending on the used IED
communication interface.
19.6.1.1
Functionality
M17109-38 v3
IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit serial
communication exchanging information with a control system. In IEC terminology
a primary station is a master and a secondary station is a slave. The communication
is based on a point-to-point principle. The master must have software that can
interpret the IEC 60870-5-103 communication messages. For detailed information
about IEC 60870-5-103, refer to IEC 60870 standard part 5: Transmission
1MRK 511 407-UEN C
Section 19
Station communication
Phasor measurement unit RES670 2.2 IEC
313
Application manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 IEC Application manual...
Page 2: ......
Page 46: ...40...
Page 52: ...46...
Page 92: ...86...
Page 112: ...106...
Page 178: ...172...
Page 216: ...210...
Page 232: ...226...
Page 286: ...280...
Page 328: ...322...
Page 340: ...334...
Page 380: ...374...
Page 381: ...375...