where it is considered that:
the operate time of overcurrent protection B1 is 40 ms
the breaker open time
is 100 ms
the resetting time of protection A1
is 40 ms and
the additional margin
is 40 ms
8.2
Directional residual overcurrent protection, four
steps EF4PTOC
IP14509-1 v8
8.2.1
Identification
M14881-1 v6
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Directional residual overcurrent
protection, four steps
EF4PTOC
4(IN>)
4
alt
4
TEF-REVA V2 EN-US
51N_67N
8.2.2
Setting guidelines
IP14988-1 v1
M15282-3 v12
When inverse time overcurrent characteristic is selected, the
operate time of the stage will be the sum of the inverse time delay
and the set definite time delay. Thus, if only the inverse time delay
is required, it is important to set the definite time delay for that
stage to zero.
The parameters for the four step residual overcurrent protection are set via the local
HMI or PCM600. The following settings can be done for the function.
Common base IED values for the primary current (
IBase
), primary voltage (
UBase
)
and primary power (
SBase
) are set in global base values for settings function
GBASVAL.
GlobalBaseSel
: Selects the global base value group used by the function to define
IBase
,
UBase
and
SBase
as applicable.
Section 8
1MRK 511 407-UEN C
Current protection
134
Phasor measurement unit RES670 2.2 IEC
Application manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 IEC Application manual...
Page 2: ......
Page 46: ...40...
Page 52: ...46...
Page 92: ...86...
Page 112: ...106...
Page 178: ...172...
Page 216: ...210...
Page 232: ...226...
Page 286: ...280...
Page 328: ...322...
Page 340: ...334...
Page 380: ...374...
Page 381: ...375...