6.2.5
Settings
Table 33:
FDPSPDIS Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
21 enable
Disabled
Enabled
-
-
Enabled
Operation of impedance based measurement
50/51 enable
Disabled
Enabled
-
-
Disabled
Operation of current based measurement
3I0BLK_PP
10 - 100
%IPh
1
40
3I0 limit for blocking Phase-to-Phase
measuring loops
3I0Enable_PG
10 - 100
%IPh
1
20
3I0 limit for releasing Phase-to-Ground
measuring loops
RLdFwd
1.00 - 3000.00
ohm/p
0.01
80.00
Forward resistive reach for the load impedance
area
RldRev
1.00 - 3000.00
ohm/p
0.01
80.00
Reverse resistive reach for the load impedance
area
LdAngle
5 - 70
Deg
1
30
Load angle determining the load impedance
area
X0
0.50 - 3000.00
-
0.01
120.00
Zero sequence reactance reach
Pickup Iph
10 - 2500
%IB
1
120
Pick up value for phase selection by over-
current element
Pickup_N
10 - 2500
%IB
1
20
3I0 pickup
X1
0.50 - 3000.00
-
0.01
40.00
Positive sequence reactance reach
RFltFwdPP
0.50 - 3000.00
ohm/l
0.01
30.00
Fault resistance reach, Phase-Phase, forward
RFltRevPP
0.50 - 3000.00
ohm/l
0.01
30.00
Fault resistance reach, Phase-Phase, reverse
RFltFwdPG
1.00 - 9000.00
ohm/l
0.01
100.00
Fault resistance reach, Phase-Ground,
forward
RFltRevPG
1.00 - 9000.00
ohm/l
0.01
100.00
Fault resistance reach, Phase-Ground,
reverse
IMinPUPP
5 - 500
%IB
1
10
Minimum pickup delta current (2 x current of
lagging phase) for Phase-to-phase loops
IMinPUPG
5 - 500
%IB
1
5
Minimum pickup phase current for Phase-to-
ground loops
Table 34:
FDPSPDIS Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
TimerPP
Disabled
Enabled
-
-
Disabled
Operation mode Off / On of zone timer, Phase-
Phase
tPP
0.000 - 60.000
s
0.001
3.000
Time delay to trip, Phase-Phase
TimerPE
Disabled
Enabled
-
-
Disabled
Operation mode Off / On of zone timer, Phase-
Ground
tPG
0.000 - 60.000
s
0.001
3.000
Time delay to trip, Ground-Earth
1MRK 506 335-UUS A
Section 6
Impedance protection
129
Technical manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Page 2: ......
Page 42: ...36 ...
Page 48: ...42 ...
Page 58: ...52 ...
Page 68: ...62 ...
Page 74: ...68 ...
Page 194: ...188 ...
Page 534: ...528 ...
Page 580: ...574 ...
Page 722: ...716 ...
Page 792: ...786 ...
Page 855: ...849 ...