6.8.7
Technical data
Table 70:
ZCVPSOF technical data
Parameter
Range or value
Accuracy
Operate voltage, detection of dead line
(1–100)% of
VBase
± 0.5% of V
n
Operate current, detection of dead line
(1–100)% of
IBase
± 1.0% of I
n
Delay following dead line detection input before
Automatic switch into fault logic function is
automatically enabled
(0.000–60.000) s
± 0.5% ± 10 ms
Time period after circuit breaker closure in which
Automatic switch into fault logic function is active
(0.000–60.000) s
± 0.5% ± 10 ms
1MRK 506 335-UUS A
Section 6
Impedance protection
187
Technical manual