14.21.2
Function block
I103AR
BLOCK
16_ARACT
128_CBON
130_BLKD
IEC10000289-2-en.vsd
IEC10000289 V2 EN
Figure 326:
I103AR function block
14.21.3
Signals
Table 519:
I103AR Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of status reporting
16_ARACT
BOOLEAN
0
Information number 16, auto-recloser active
128_CBON
BOOLEAN
0
Information number 128, circuit breaker on by auto-
recloser
130_BLKD
BOOLEAN
0
Information number 130, auto-recloser blocked
14.21.4
Settings
Table 520:
I103AR Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type (1-255)
14.22
Function status ground-fault for IEC 60870-5-103
I103EF
14.22.1
Functionality
I103EF is a function block with defined functions for ground fault indications in monitor
direction. This block includes the
FunctionType
parameter, and the information number
parameter is defined for each output signal.
1MRK 506 335-UUS A
Section 14
Monitoring
699
Technical manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Page 2: ......
Page 42: ...36 ...
Page 48: ...42 ...
Page 58: ...52 ...
Page 68: ...62 ...
Page 74: ...68 ...
Page 194: ...188 ...
Page 534: ...528 ...
Page 580: ...574 ...
Page 722: ...716 ...
Page 792: ...786 ...
Page 855: ...849 ...