![ABB REL650 series Technical Manual Download Page 574](http://html.mh-extra.com/html/abb/rel650-series/rel650-series_technical-manual_4784574.webp)
Name
Type
Description
OUT10
BOOLEAN
Output 10
OUT11
BOOLEAN
Output 11
OUT12
BOOLEAN
Output 12
OUT13
BOOLEAN
Output 13
OUT14
BOOLEAN
Output 14
OUT15
BOOLEAN
Output 15
OUT16
BOOLEAN
Output 16
13.9.5
Settings
The function does not have any parameters available in local HMI or Protection and
Control IED Manager (PCM600)
13.9.6
Operation principle
An example is used to explain the principle of operation: With integer 15 sent to and
received by the IB16FCVB function on the IEC 61850 the OUTx changes from 0 to 1 on
each of the OUT1; OUT2 OUT3 and OUT4. All other OUTx (5≤x≤16) remains 0. The
boolean interpretation of this is represented by the assigned values of each of the outputs
OUT1 = 1; and OUT2 = 2; and OUT3= 4; and OUT4 = 8. The sum of these OUTx (1≤x≤4)
is equal to the integer 15 received via the IEC 61850 network. The remaining OUTx = 0
for (5≤x≤16).
OUTx represents a value when activated. The value of each of the OUTx is in accordance
with the Table
. When not activated the OUTx has the value 0.
The value of each OUTx for 1≤x≤16 (1≤x≤16) follows the general formulae: OUTx = 2
x-1
The sum of the values of all activated OUTx = 2
x-1
where 1≤x≤16 will be equal to the
integer value received over IEC 61850 to the IB16FCVB_1 function block.
The Integer to Boolean 16 conversion with logic node representation function
(IB16FCVB) will transfer an integer with a value between 0 to 65535 communicated via
IEC 61850 and connected to the IB16FCVB function block to a combination of activated
outputs OUTx where 1≤x≤16. The values represented by the different OUTx are
according to Table
. When an OUTx is not activated, its value is 0.
The IB16FCVB function is designed for receiving the integer input from a station
computer - for example, over IEC 61850. If the BLOCK input is activated, it will freeze
the logical outputs at the last value.
Section 13
1MRK 506 335-UUS A
Logic
568
Technical manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Page 2: ......
Page 42: ...36 ...
Page 48: ...42 ...
Page 58: ...52 ...
Page 68: ...62 ...
Page 74: ...68 ...
Page 194: ...188 ...
Page 534: ...528 ...
Page 580: ...574 ...
Page 722: ...716 ...
Page 792: ...786 ...
Page 855: ...849 ...