Actual value of the measured quantity
The actual value of the measured quantity is available locally and remotely. The
measurement is continuous for each measured quantity separately, but the reporting of the
value to the higher levels depends on the selected reporting mode. The following basic
reporting modes are available:
•
Cyclic reporting (
Cyclic
)
•
Magnitude dead-band supervision (
Dead band
)
•
Integral dead-band supervision (
Int deadband
)
Cyclic reporting
The cyclic reporting of measured value is performed according to chosen setting
(
XRepTyp
). The measuring channel reports the value independent of magnitude or
integral dead-band reporting.
In addition to the normal cyclic reporting the IED also report spontaneously when
measured value passes any of the defined threshold limits.
en05000500.vsd
V
a
lu
e
1
Y
t
V
a
lu
e
2
V
a
lu
e
3
V
a
lu
e
4
Value Reported
(1st)
Value Reported
V
a
lu
e
5
Value Reported
Y1
Y2
Y5
Value Reported
Value Reported
Y3
Y4
(*)Set value for t: XDbRepInt
t (*)
t (*)
t (*)
t (*)
IEC05000500 V1 EN
Figure 286:
Periodic reporting
1MRK 506 335-UUS A
Section 14
Monitoring
597
Technical manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Page 2: ......
Page 42: ...36 ...
Page 48: ...42 ...
Page 58: ...52 ...
Page 68: ...62 ...
Page 74: ...68 ...
Page 194: ...188 ...
Page 534: ...528 ...
Page 580: ...574 ...
Page 722: ...716 ...
Page 792: ...786 ...
Page 855: ...849 ...