
11.11.3
Signals
Table 317:
I103CMD Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of commands
Table 318:
I103CMD Output signals
Name
Type
Description
16-AR
BOOLEAN
Information number 16 disable/enable autorecloser
17-DIFF
BOOLEAN
Information number 17, block of differential protection
18-PROT
BOOLEAN
Information number 18, block of protection
11.11.4
Settings
Table 319:
I103CMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type (1-255)
11.12
IED commands for IEC 60870-5-103 I103IEDCMD
11.12.1
Functionality
I103IEDCMD is a command block in control direction with defined IED functions. All
outputs are pulsed and they are NOT stored. Pulse length is fixed to 400ms.
11.12.2
Function block
IEC10000283-1-en.vsd
I103IEDCMD
BLOCK
19-LEDRS
23-GRP1
24-GRP2
25-GRP3
26-GRP4
IEC10000283 V1 EN
Figure 225:
I103IEDCMD function block
1MRK 506 335-UUS A
Section 11
Control
489
Technical manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Page 2: ......
Page 42: ...36 ...
Page 48: ...42 ...
Page 58: ...52 ...
Page 68: ...62 ...
Page 74: ...68 ...
Page 194: ...188 ...
Page 534: ...528 ...
Page 580: ...574 ...
Page 722: ...716 ...
Page 792: ...786 ...
Page 855: ...849 ...