![ABB REL650 series Technical Manual Download Page 815](http://html.mh-extra.com/html/abb/rel650-series/rel650-series_technical-manual_4784815.webp)
Description
Type test value
Reference
88 – 216 MHz
< 43,52 dB(µV/m) quasi peak,
measured at 10 m distance
216 – 960 MHz
< 46,44 dB(µV/m) quasi peak,
measured at 10 m distance
960 – 1000 MHz
< 49,54 dB(µV/m) quasi peak,
measured at 10 m distance
20.2
Insulation tests
Table 652:
Insulation tests
Description
Type test value
Reference
Dielectric tests:
IEC 60255-5
ANSI C37.90-2005
•
Test voltage
2 kV, 50 Hz, 1 min
1 kV, 50 Hz, 1 min,
communication
Impulse voltage test:
IEC 60255-5
ANSI C37.90-2005
•
Test voltage
5 kV, unipolar impulses,
waveform 1.2/50 μs, source
energy 0.5 J
1 kV, unipolar impulses,
waveform 1.2/50 μs, source
energy 0.5 J, communication
Insulation resistance
measurements
IEC 60255-5
ANSI C37.90-2005
•
Isolation resistance
>100 MΏ, 500 V DC
Protective bonding resistance
IEC 60255-27
•
Resistance
<0.1 Ώ (60 s)
20.3
Mechanical tests
Table 653:
Mechanical tests
Description
Reference
Requirement
Vibration response tests
(sinusoidal)
IEC 60255-21-1
Class 1
Vibration endurance test
IEC60255-21-1
Class 1
Shock response test
IEC 60255-21-2
Class 1
Table continues on next page
1MRK 506 335-UUS A
Section 20
IED and functionality tests
809
Technical manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Page 2: ......
Page 42: ...36 ...
Page 48: ...42 ...
Page 58: ...52 ...
Page 68: ...62 ...
Page 74: ...68 ...
Page 194: ...188 ...
Page 534: ...528 ...
Page 580: ...574 ...
Page 722: ...716 ...
Page 792: ...786 ...
Page 855: ...849 ...