12.1.7
Technical data
Table 336:
ZCPSCH (85) technical data
Function
Range or value
Accuracy
Scheme type
Disabled
Intertrip
Permissive UR
Permissive OR
Blocking
DeltaBlocking
-
Operate voltage, Delta V
(0–100)% of VBase
± 5.0% of ΔV
Operate current, Delta I
(0–200)% of IBase
± 5.0% of ΔI
Operate zero sequence voltage,
Delta 3V0
(0–100)% of VBase
± 10.0% of Δ3V0
Operate zero sequence current,
Delta 3I0
(0–200)% of IBase
± 10.0% of Δ3I0
Co-ordination time for blocking
communication scheme
(0.000-60.000) s
± 0.5% ± 10 ms
Minimum duration of a carrier send
signal
(0.000-60.000) s
± 0.5% ± 10 ms
Security timer for loss of guard signal
detection
(0.000-60.000) s
± 0.5% ± 10 ms
Operation mode of unblocking logic
Disabled
NoRestart
Restart
-
12.2
Current reversal and WEI logic for distance protection
3-phase ZCRWPSCH (85)
12.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Current reversal and WEI logic for
distance protection 3-phase
ZCRWPSCH
-
85
12.2.2
Functionality
The current reversal function is used to prevent unwanted operations due to current
reversal when using permissive overreach or unblock protection or unblocking schemes
in application with parallel lines.
Section 12
1MRK 506 335-UUS A
Scheme communication
502
Technical manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Page 2: ......
Page 42: ...36 ...
Page 48: ...42 ...
Page 58: ...52 ...
Page 68: ...62 ...
Page 74: ...68 ...
Page 194: ...188 ...
Page 534: ...528 ...
Page 580: ...574 ...
Page 722: ...716 ...
Page 792: ...786 ...
Page 855: ...849 ...