apparent impedances at phase-to-phase faults follow equation
to phase B fault).
=
V
A
- V
B
Z
app
I
A
- I
B
EQUATION1545 V1 EN
(Equation 23)
Here V and I represent the corresponding voltage and current phasors in the respective
phase Ln (n = 1, 2, 3)
The ground return compensation applies in a conventional manner to phase-to-ground
faults (example for a phase A to ground fault) according to equation
.
=
+ ×
app
N
V _ A
Z
I _ A I KN
EQUATION1546 V1 EN
(Equation 24)
Where:
V_A, I_A and IN
are the phase voltage, phase current and residual current present to the IED
KN is defined as:
Z0 Z1
KN
3 Z1
-
=
×
EQUATION-2105 V1 EN
0
0
0
Z
R
jX
=
+
EQUATION2106 V1 EN
1
1
1
Z
R
jX
=
+
EQUATION2107 V1 EN
Where
R0
is the resistive zero sequence reach
X0
is the reactive zero sequence reach
R1
is the resistive positive sequence reach
X1
is the reactive positive sequence reach
Here IN is a phasor of the residual current in IED point. This results in the same reach
along the line for all types of faults.
1MRK 506 335-UUS A
Section 6
Impedance protection
121
Technical manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Page 2: ......
Page 42: ...36 ...
Page 48: ...42 ...
Page 58: ...52 ...
Page 68: ...62 ...
Page 74: ...68 ...
Page 194: ...188 ...
Page 534: ...528 ...
Page 580: ...574 ...
Page 722: ...716 ...
Page 792: ...786 ...
Page 855: ...849 ...