Table 483:
MVGGIO Output signals
Name
Type
Description
VALUE
REAL
Magnitude of deadband value
RANGE
INTEGER
Range
14.12.5
Settings
Table 484:
MVGGIO Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
BasePrefix
micro
milli
unit
kilo
Mega
Giga
Tera
-
-
unit
Base prefix (multiplication factor)
MV db
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
MV zeroDb
0 - 100000
m%
1
500
Zero point clamping in 0.001% of range
MV hhLim
-5000.00 - 5000.00
xBase
0.01
900.00
High High limit multiplied with the base prefix
(multiplication factor)
MV hLim
-5000.00 - 5000.00
xBase
0.01
800.00
High limit multiplied with the base prefix
(multiplication factor)
MV lLim
-5000.00 - 5000.00
xBase
0.01
-800.00
Low limit multiplied with the base prefix
(multiplication factor)
MV llLim
-5000.00 - 5000.00
xBase
0.01
-900.00
Low Low limit multiplied with the base prefix
(multiplication factor)
MV min
-5000.00 - 5000.00
xBase
0.01
-1000.00
Minimum value multiplied with the base prefix
(multiplication factor)
MV max
-5000.00 - 5000.00
xBase
0.01
1000.00
Maximum value multiplied with the base prefix
(multiplication factor)
MV dbType
Cyclic
Dead band
Int deadband
-
-
Dead band
Reporting type
MV limHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range (common for all
limits)
1MRK 506 335-UUS A
Section 14
Monitoring
659
Technical manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Page 2: ......
Page 42: ...36 ...
Page 48: ...42 ...
Page 58: ...52 ...
Page 68: ...62 ...
Page 74: ...68 ...
Page 194: ...188 ...
Page 534: ...528 ...
Page 580: ...574 ...
Page 722: ...716 ...
Page 792: ...786 ...
Page 855: ...849 ...