Name
Values (Range)
Unit
Step
Default
Description
t2
0.000 - 60.000
s
0.001
0.400
Independent (definite) time delay of step 2
IMin2
1 - 10000
%IB
1
50
Minimum operate current for step 2 in % of
IBase
HarmRestrain2
Off
On
-
-
On
Enable block of step 2 from harmonic restrain
DirMode3
Off
Non-directional
Forward
Reverse
-
-
Non-directional
Directional mode of step 3 (off, non-directional,
forward, reverse)
IN3>
1 - 2500
%IB
1
33
Operate residual current level for step 3 in % of
IBase
t3
0.000 - 60.000
s
0.001
0.800
Independent (definite) time delay of step 3
IMin3
1 - 10000
%IB
1
33
Minimum operate current for step 3 in % of
IBase
HarmRestrain3
Off
On
-
-
On
Enable block of step 3 from harmonic restrain
DirMode4
Off
Non-directional
Forward
Reverse
-
-
Non-directional
Directional mode of step 4 (off, non-directional,
forward, reverse)
Characterist4
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
RI type
RD type
-
-
ANSI Def. Time
Time delay curve type for step 4
IN4>
1 - 2500
%IB
1
17
Operate residual current level for step 4 in % of
IBase
t4
0.000 - 60.000
s
0.001
1.200
Independent (definite) time delay of step 4
k4
0.05 - 999.00
-
0.01
0.05
Time multiplier for the dependent time delay for
step 4
IMin4
1 - 10000
%IB
1
17
Minimum operate current for step 4 in % of
IBase
t4Min
0.000 - 60.000
s
0.001
0.000
Minimum operate time in inverse curves step 4
HarmRestrain4
Off
On
-
-
On
Enable block of step 4 from harmonic restrain
1MRK 506 335-UUS A
Section 7
Current protection
219
Technical manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Page 2: ......
Page 42: ...36 ...
Page 48: ...42 ...
Page 58: ...52 ...
Page 68: ...62 ...
Page 74: ...68 ...
Page 194: ...188 ...
Page 534: ...528 ...
Page 580: ...574 ...
Page 722: ...716 ...
Page 792: ...786 ...
Page 855: ...849 ...