7.3.9
Technical data
Table 89:
OC4PTOC (51/67) technical data
Function
Setting range
Accuracy
Operate current
(5-2500)% of
lBase
±
1.0% of I
n
at I ≤ I
n
±
1.0% of I at I > I
n
Reset ratio
> 95% at (50–2500)% of
lBase
-
Min. operating current
(5-10000)% of
lBase
±
1.0% of I
n
at I ≤ I
n
±
1.0% of I at I > I
n
2nd harmonic blocking
(5–100)% of fundamental
±
2.0% of I
n
Independent time delay
(0.000-60.000) s
±
0.5%
±
25 ms
Minimum operate time for
inverse characteristics
(0.000-60.000) s
±
0.5%
±
25 ms
Inverse characteristics, see
and table
15 curve types
1)
ANSI/IEEE C37.112
IEC 60255–151
±
3% or
±
40 ms
0.10 ≤ k ≤ 3.00
1.5 x I
set
≤ I ≤ 20 x I
set
Operate time, nondirectional
pickup function
25 ms typically at 0 to 2 x I
set
-
Reset time, pickup function
35 ms typically at 2 to 0 x I
set
-
Operate time, directional pickup
function
50 ms typically at 0 to 2 x I
set
-
Reset time, directional pickup
function
35 ms typically at 2 to 0 x I
set
-
Critical impulse time
10 ms typically at 0 to 2 x I
set
-
Impulse margin time
15 ms typically
-
1)
Note: Timing accuracy only valid when 2nd harmonic blocking is turned off
7.4
Four step phase overcurrent protection phase
segregated output OC4SPTOC (51/67)
7.4.1
Identification
Function description
IEC 61850 identification
IEC 60617 identification
ANSI/IEEE C37.2 device
number
Four step phase
overcurrent protection,
phase segregated
output
OC4SPTOC
ID-2147.VSD V1 EN
51/67
Section 7
1MRK 506 335-UUS A
Current protection
204
Technical manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Page 2: ......
Page 42: ...36 ...
Page 48: ...42 ...
Page 58: ...52 ...
Page 68: ...62 ...
Page 74: ...68 ...
Page 194: ...188 ...
Page 534: ...528 ...
Page 580: ...574 ...
Page 722: ...716 ...
Page 792: ...786 ...
Page 855: ...849 ...