
8.3.5
Settings
Table 197:
ROV2PTOV (59N) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Disable/Enable Operation
OperationStep1
Disabled
Enabled
-
-
Enabled
Enable execution of step 1
Characterist1
Definite time
Inverse curve A
Inverse curve B
Inverse curve C
-
-
Definite time
Selection of time delay curve type for step 1
Pickup1
1 - 200
%VB
1
30
Voltage start value (DT & IDMT) in % of VBase
for step 1
t1
0.00 - 6000.00
s
0.01
5.00
Definite time delay of step 1
t1Min
0.000 - 60.000
s
0.001
5.000
Minimum operate time for inverse curves for
step 1
TD1
0.05 - 1.10
-
0.01
0.05
Time multiplier for the inverse time delay for
step 1
OperationStep2
Disabled
Enabled
-
-
Enabled
Enable execution of step 2
Pickup2
1 - 100
%VB
1
45
Voltage start value (DT & IDMT) in % of VBase
for step 2
t2
0.000 - 60.000
s
0.001
5.000
Definite time delay of step 2
Table 198:
ROV2PTOV (59N) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
8.3.6
Monitored data
Table 199:
ROV2PTOV (59N) Monitored data
Name
Type
Values (Range)
Unit
Description
VLevel
REAL
-
kV
Magnitude of measured
voltage
8.3.7
Operation principle
Two step residual overvoltage protection ROV2PTOV (59N) is used to detect ground
(zero sequence) overvoltages. The ground overvoltage 3V
0
is normally computed by
1MRK 506 335-UUS A
Section 8
Voltage protection
309
Technical manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Page 2: ......
Page 42: ...36 ...
Page 48: ...42 ...
Page 58: ...52 ...
Page 68: ...62 ...
Page 74: ...68 ...
Page 194: ...188 ...
Page 534: ...528 ...
Page 580: ...574 ...
Page 722: ...716 ...
Page 792: ...786 ...
Page 855: ...849 ...